{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D56806","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D56806","canonicalUrl":"https://aoctrl.com/schneider/A9D56806","factsUrl":"https://aoctrl.com/api/mcp/products/A9D56806","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, 1P+N, 6 A, B curve, 10 kA, 30 mA, thermal-magnetic, IP20, white.","salesMarkdown":"The Schneider Electric A9D56806 is an Acti9 iC60 RCBO — a combined residual current breaker with overcurrent protection in a 1P+N, 18 mm wide modular package. It protects a single pole against overload and short-circuit (B curve, 3–5 x In magnetic trip) and adds integrated earth-leakage protection at 30 mA sensitivity, all in one DIN-rail module. Rated 6 A at 50 °C with a breaking capacity of 10 kA Icn at 240 V AC (IEC 61009-2-2), it's sized for final subcircuits in TN earthing systems — think lighting, socket outlets, or small appliance feeds where you need both overcurrent and earth-leakage protection in a single slot. The thermal-magnetic trip unit handles the overcurrent side; the integrated residual current module covers the 30 mA leakage. IP20 on the terminals, IP40 inside the modular enclosure — fine for dry indoor distribution boards. Neutral on the left, phase on the right — standard Acti9 layout. Wire stripping length is 14 mm top, 13 mm bottom. Tightening torque: 3.5 N·m on the top screw clamp, 2 N·m on the bottom. The toggle gives local ON/OFF and fault indication — useful for quick visual checks on the panel door. Rated for 5,000 electrical cycles and 20,000 mechanical cycles.","metaTitle":"Schneider Electric A9D56806 Acti9 iC60 RCBO, 6 A, B Curve, 1","metaDescription":"Schneider Electric A9D56806 Acti9 iC60H RCBO PoN. 6 A rated, B curve, 10 kA breaking capacity, 30 mA earth leakage. Active production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"BS EN 61009-1 IEC 61009-1 IEC 61009-2-2","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Plug-on","Surge current":"250 A","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication Fault indication","Mounting support":"Isobar A Isobar B","Neutral position":"Left","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IEC 61009-2-2","Device short name":"iC60H RCBO PoN","Network frequency":"50/60 Hz","Poles description":"1P + Ns","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top 2 N.m bottom","[In] rated current":"6 A at 50 °C","Overvoltage category":"II","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top connection 13 mm for bottom connection","Connections - terminals":"Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...10 mm² flexible Screw clamp terminal (top) 1...25 mm² rigid Screw clamp terminal (bottom) 1...16 mm² rigid Plug-on neutral (upstream)","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Electrical insulation class":"Class II","Locking options description":"Padlock in on or off position","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 240 V AC 50/60 Hz conforming to IEC 61009-2-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$197.56","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/uk/en/product/A9D56806/acti9-ic60h-rcbo-plug-on-neutral-1p+ns-6a-b-10000a-30ma-type-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D56806/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D56806 and get pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What is the closest alternative to A9D56806 in the Acti9 family?","answer":"Within the Acti9 iC60 range, the main variant differences are rated current (In), curve (B/C/D), and earth-leakage sensitivity. The A9D56806 is a 6 A B-curve 30 mA unit; a higher-current or different-curve sibling would share the same footprint and terminal specs but change the protection characteristic."},{"question":"What compliance documentation does this RCBO carry?","answer":"Certified to BS EN 61009-1, IEC 61009-1, and IEC 61009-2-2. The IP ratings are IP20 (terminals) and IP40 (modular enclosure) per IEC 60529."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D56806","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D56806 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}