{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D57416","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D57416","canonicalUrl":"https://aoctrl.com/schneider/A9D57416","factsUrl":"https://aoctrl.com/api/mcp/products/A9D57416","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, 4P, 16 A, 30 mA, C-curve, 6 kA Icn, clip-on DIN rail, white.","salesMarkdown":"The integrated earth-leakage protection is set at 30 mA sensitivity, the standard for personal shock protection in IEC 60364 circuits. Breaking capacity is 6 kA Icn at 380...415 V AC 50 Hz per EN/IEC 61009-2-1, and 6 kA Icu per EN/IEC 60947-2 — sufficient for most final subcircuits in commercial and light industrial panels where the prospective fault current is below that threshold. Clip-on mounting to DIN rail (9 mm pitch between poles, 8 pitches occupied) means it snaps into a standard distribution board without tools. Mounts via clip-on to DIN rail. The unit occupies 8 pitches of 9 mm (72 mm total width), which is standard for a 4-pole RCBO in the Acti9 range. IP40 in a distribution enclosure, IP20 otherwise — no washdown rating, so it stays inside a cabinet. Local signalling shows ON, OFF, and fault trip via the toggle position.","metaTitle":"Schneider Electric A9D57416 Acti9 iC60 RCBO, 4P, 16 A, 30 mA","metaDescription":"Schneider Electric A9D57416 Acti9 iC60 RCBO, 4-pole, 16 A rated current, 30 mA earth leakage, C-curve, 6 kA breaking capacity. Active production — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"78 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"86 mm","Standards":"EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"250 A","Quality labels":"VDE KEMA-KEUR NF IMQ","Tropicalisation":"2","lifecycle_stage":"current","Connection pitch":"9 mm between poles","Limitation class":"1 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iC60 RCBO","Network frequency":"50 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"4","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"No conforming to IEC 60947-1","Contact position indicator":"No","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"380...415 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA 100 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES Bottom: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/A9D57416/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60-4p-16a-c-curve-6000a-6ka-ac-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D57416/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9D57416?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest pin-compatible alternative to A9D57416 in this component family?","answer":"Within the Acti9 iC60 RCBO family, the nearest sibling differs only by rated current or earth-leakage sensitivity — the same 4-pole C-curve form factor and DIN-rail footprint are shared across the range. The deciding factor for substitution is the BOM's required In and IΔn values."},{"question":"What is A9D57416's listed depth (78 mm) on this component line?","answer":"The depth is 78 mm, with a height of 86 mm and width of 72 mm (8 pitches at 9 mm). These dimensions fit standard Acti9 distribution board cutouts."},{"question":"What compliance documentation does this brand provide for A9D57416 (RoHS, REACH, UL, IEC)?","answer":"The part is certified to EN/IEC 60947-2 and EN/IEC 61009-2-1, carries quality labels VDE, KEMA-KEUR, NF, and IMQ, and is designed for overvoltage category III per IEC 60364. RoHS and REACH declarations are available from the manufacturer's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D57416","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D57416 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}