{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D57432","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D57432","canonicalUrl":"https://aoctrl.com/schneider/A9D57432","factsUrl":"https://aoctrl.com/api/mcp/products/A9D57432","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, 4P, 32 A rated current, 30 mA earth-leakage sensitivity, C-curve, 6 kA breaking capacity, clip-on DIN rail mount.","salesMarkdown":"Its 32 A rated current (In) and C-curve magnetic trip (5 to 10 x In) mean it is sized for general-purpose distribution circuits feeding mixed resistive and moderate-inductive loads, such as lighting, socket outlets, and small motorized equipment, where the C-curve provides tolerance for inrush without nuisance tripping. The 30 mA earth-leakage sensitivity (IΔn) provides personnel protection against direct contact, per the requirements of IEC 60364 for socket-outlet circuits and final subcircuits in residential and commercial installations. Integrated earth-leakage protection means no separate RCCB module is needed upstream — this single unit handles both overcurrent and ground-fault detection. Breaking capacity is 6 kA Icn / Icu at 380–415 V AC, 50 Hz, conforming to EN/IEC 61009-2-1 and EN/IEC 60947-2. This is the standard interrupting rating for final distribution boards in most European domestic and light commercial panels. For installations with higher prospective fault current, selectivity with an upstream MCCB or fuse must be verified. The thermal-magnetic trip unit provides time-delayed overload protection (thermal bimetal) and instantaneous short-circuit protection (magnetic solenoid). Limitation class 1 per EN/IEC 61009-2-1 means the device limits let-through energy to a level that protects downstream wiring under fault conditions. ## Deployment and integration Clip-on mounting to DIN rail (EN 60715) with a 9 mm pole pitch. The 4-pole unit occupies 8 x 9 mm = 72 mm of rail width. IP40 in a distribution enclosure, IP20 for the terminals — suitable for installation within a panel or consumer unit. Local signalling via toggle position: ON, OFF, and fault-trip indication. The toggle provides manual control and visual status at the panel face. Quality labels include KEMA-KEUR, NF, IMQ, and VDE — these marks certify compliance with the applicable EN/IEC standards and are accepted across most European and many international regulatory jurisdictions. ## Durability and environmental ratings These figures reflect the expected service life under rated load conditions and are consistent with a premium RCBO intended for distribution duty.","metaTitle":"Schneider Electric A9D57432 Acti9 iC60 RCBO, 32A, 30mA, 4P,","metaDescription":"Schneider Electric A9D57432 Acti9 iC60 RCBO. 32A rated current, 30mA earth leakage, 4-pole, C-curve, 6kA breaking capacity. Active production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"78 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"86 mm","Standards":"EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"250 A","Quality labels":"KEMA-KEUR NF IMQ VDE","Tropicalisation":"2","lifecycle_stage":"current","Connection pitch":"9 mm between poles","Limitation class":"1 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iC60 RCBO","Network frequency":"50 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"4","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"No conforming to IEC 60947-1","Contact position indicator":"No","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"380...415 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA 100 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES Bottom: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/A9D57432/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60-4p-32a-c-curve-6000a-6ka-ac-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D57432/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for A9D57432?","answer":"The A9D57432 carries KEMA-KEUR, NF, IMQ, and VDE quality labels, and is certified to EN/IEC 60947-2 and EN/IEC 61009-2-1. RoHS and REACH compliance documentation is standard for Schneider Electric Acti9 products; request these from the distributor at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D57432","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D57432 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}