{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D60610","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D60610","canonicalUrl":"https://aoctrl.com/schneider/A9D60610","factsUrl":"https://aoctrl.com/api/mcp/products/A9D60610","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi RCBO, 1P+N, 10 A, B-curve, 6 kA breaking capacity, 100 mA earth leakage, DIN rail clip-on, white.","salesMarkdown":"The Schneider Electric A9D60610 is an Acti9 iDPN Vigi residual-current circuit breaker with overcurrent protection (RCBO) — a single-module device combining a 10 A thermal-magnetic MCB with integrated 100 mA earth-leakage detection in a 1P+N format. The 6 kA breaking capacity at 230–240 V AC, 50 Hz, conforms to EN/IEC 61009-2-1, the standard governing combined RCBOs for household and similar installations. The 10 A rated current (In) sets the continuous load limit for the protected circuit — downstream wiring and loads must stay under this figure. The B-curve magnetic trip (3–5 x In) means the breaker holds through normal resistive start-up but clears quickly on a hard short; it is the standard choice for lighting, socket outlets, and control transformers where no motor inrush is present. The 100 mA earth-leakage sensitivity (IΔn) provides personnel protection against indirect contact and fire risk from ground faults; it is less sensitive than 30 mA units, so it is better suited for circuits with higher natural leakage (long cable runs, multiple loads) where nuisance tripping is a concern. This RCBO is designed for distribution boards (outgoer position) in final sub-circuits. The toggle provides local ON/OFF/fault-trip indication, so a tripped RCBO shows a distinct mid-position. ## Termination and wiring notes Strip length is 15 mm. The connection pitch is 9 mm between phase and neutral, matching standard busbar systems for the Acti9 range. Mechanical and electrical durability are both rated at 20,000 cycles — adequate for normal switching duty in a distribution board. Relative humidity tolerance is 95% at 55 °C. The standard cited is EN/IEC 61009-2-1, which covers RCBOs for household and similar uses. No UL or CSA listing is stated in the evidence — this part is designed for IEC markets.","metaTitle":"Schneider Electric A9D60610 Acti9 iDPN Vigi RCBO, 10A B-curv","metaDescription":"Schneider Electric A9D60610 Acti9 iDPN Vigi RCBO, 10A rated, B-curve, 6kA breaking capacity, 100mA earth leakage, DIN rail mount, EN/IEC 61009-2-1. Current production, sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/my/en/product/A9D60610/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-idpn-n-vigi-1p+n-10a-b-curve-6000a-a-type-100ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D60610/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the A9D60610?","answer":"The A9D60610 has a breaking capacity of 6000 A Icn at 230–240 V AC, 50 Hz, conforming to EN/IEC 61009-2-1."},{"question":"What is the earth-leakage sensitivity of this RCBO?","answer":"The integrated earth-leakage protection is set to 100 mA sensitivity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D60610","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D60610 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}