{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D60616","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D60616","canonicalUrl":"https://aoctrl.com/schneider/A9D60616","factsUrl":"https://aoctrl.com/api/mcp/products/A9D60616","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi RCBO, 1P+N, 16 A, 30 mA, curve B, 6 kA breaking capacity, DIN rail mount.","salesMarkdown":"It combines a thermal-magnetic overcurrent trip (curve B, 3...5 x In magnetic threshold) and integrated earth-leakage protection in a single 1P+N module, saving a DIN-rail position compared to a separate MCB and RCCB. Breaking capacity is 6000 A Icn at 230...240 V AC, 50 Hz, per EN/IEC 61009-2-1 — sufficient for most residential and light commercial distribution boards where the prospective short-circuit current stays under that threshold. The limitation class 3 rating means it limits let-through energy well, aiding downstream coordination. ## Installation and mounting Clip-on mounting to DIN rail, occupying 4 pitches at 9 mm per pole (36 mm total width). Neutral is on the left, phase on the right — check busbar orientation before committing the assembly. Terminals accept 1...16 mm² rigid or 1...10 mm² flexible (with or without ferrule); tightening torque is 2 N.m, strip length 15 mm. IP20 on the device body, IP40 inside a modular enclosure per IEC 60529. ## Environmental and durability Electrical and mechanical durability each rated at 20,000 cycles, which aligns with typical panel life in non-frequent-switching distribution roles.","metaTitle":"Schneider Electric A9D60616 Acti9 iDPN Vigi RCBO, 16 A, 30 m","metaDescription":"Schneider Electric A9D60616 Acti9 iDPN Vigi RCBO, 16 A rated current, 30 mA earth leakage, curve B, 6 kA breaking capacity, 1P+N, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/sg/en/product/A9D60616/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-idpn-n-vigi-1p+n-16a-b-curve-6000a-a-type-100ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D60616/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9D60616?","answer":"6,000 A Icn at 230...240 V AC, 50 Hz, conforming to EN/IEC 61009-2-1."},{"question":"What is the earth-leakage sensitivity of this RCBO?","answer":"30 mA sensitivity, integrated into the combined overcurrent and residual-current device."},{"question":"Where can I buy A9D60616?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D60616","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D60616 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}