{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D61616","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D61616","canonicalUrl":"https://aoctrl.com/schneider/A9D61616","factsUrl":"https://aoctrl.com/api/mcp/products/A9D61616","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi, RCBO, 1P+N, 16 A, C-curve, 30 mA, 6 kA, DIN rail.","salesMarkdown":"The 30 mA earth-leakage sensitivity covers personnel protection against indirect contact, and the 6 kA breaking capacity (Icn at 110...240 V AC, 50 Hz, per EN/IEC 61009-2-1) means it can safely clear a fault up to that level without welding its contacts shut — fine for most domestic and light commercial distribution boards where the prospective short-circuit current stays under 6 kA. The limitation class 3 rating (also per EN/IEC 61009-2-1) means it limits let-through energy well, which helps with downstream coordination. The 73 mm depth keeps it inside standard 100 mm deep enclosures. Strip length is 15 mm. The IP20 rating covers the terminals (finger-safe); inside a modular enclosure it's IP40. The pollution degree 3 rating means it's suitable for environments with conductive or dry non-conductive pollution — typical of most distribution panels that aren't sealed clean-room gear.","metaTitle":"Schneider Electric A9D61616 Acti9 iDPN Vigi, 16 A C-Curve RC","metaDescription":"Schneider Electric A9D61616 Acti9 iDPN Vigi RCBO. 16 A rated, C-curve, 30 mA earth leakage, 6 kA breaking capacity. Current production. Order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Surge current":"250 A","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 110...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"110...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 110...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 110...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9D61616/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-idpn-n-vigi-1p+n-16a-c-curve-6000a-ac-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D61616/alternatives.json"},"ai":{"faq":[{"question":"What is the A9D61616 used for?","answer":"It's a 1P+N RCBO combining 16 A overcurrent protection (C-curve) with 30 mA earth-leakage protection, used in distribution boards for final circuits supplying lighting, socket outlets, and small loads."},{"question":"What is the breaking capacity of the A9D61616?","answer":"6 kA Icn at 110...240 V AC, 50 Hz, conforming to EN/IEC 61009-2-1. That's the standard rating for most domestic and light commercial boards."},{"question":"Where can I buy the A9D61616 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through our independent distribution channel. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"What compliance documentation does Schneider provide for the A9D61616?","answer":"The part is certified to EN/IEC 61009-2-1. It carries an overvoltage category III rating per IEC 60364 and tropicalisation class 2 per IEC 60068-1. Standard Schneider documentation (declaration of conformity, CE) is available on request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D61616","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D61616 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}