{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D61632","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D61632","canonicalUrl":"https://aoctrl.com/schneider/A9D61632","factsUrl":"https://aoctrl.com/api/mcp/products/A9D61632","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi, RCBO, 1P+N, 32 A, C-curve, 30 mA earth-leakage, 6 kA Icn, DIN-rail clip-on.","salesMarkdown":"It carries a 32 A rated current (In) on a C-curve magnetic trip (5–10× In) and integrated 30 mA earth-leakage protection, all in a single 36 mm wide module that clips onto a DIN rail. The 6 kA breaking capacity (Icn at 110–240 V AC, 50 Hz, per EN/IEC 61009-2-1) suits it for final-subcircuit protection in residential and light commercial distribution boards where the prospective fault current stays under that threshold. Neutral is on the left, phase on the right. Terminals accept 1–16 mm² rigid or 1–10 mm² flexible at the top or bottom; tighten to 2 N·m with 15 mm strip length. IP20 finger-safe on the front face, IP40 inside a modular enclosure. Tropicalisation class 2 (IEC 60068-1) handles 95 % RH at 55 °C, so it's fine for coastal or unconditioned electrical rooms.","metaTitle":"Schneider Electric A9D61632 Acti9 iDPN Vigi RCBO, 32 A C-cur","metaDescription":"Schneider Electric A9D61632 Acti9 iDPN Vigi RCBO. 32 A rated current, C-curve, 30 mA earth leakage, 6 kA breaking capacity. DIN-rail mount, current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Surge current":"250 A","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 110...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"110...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 110...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 110...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9D61632/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-idpn-n-vigi-1p+n-32a-c-curve-6000a-ac-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D61632/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9D61632 and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate."},{"question":"What is the breaking capacity of the A9D61632?","answer":"6 kA Icn at 110–240 V AC, 50 Hz, conforming to EN/IEC 61009-2-1 — sufficient for final subcircuits in residential and light commercial boards with prospective fault currents under that level."},{"question":"What compliance documentation does Schneider provide for the A9D61632?","answer":"The part is certified to EN/IEC 61009-2-1 (RCBO standard) and carries IP20/IP40 ratings per IEC 60529, pollution degree 3 per IEC 60364, and tropicalisation class 2 per IEC 60068-1. Standard Schneider declarations of conformity and CE marking apply."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D61632","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D61632 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}