{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D61806","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D61806","canonicalUrl":"https://aoctrl.com/schneider/A9D61806","factsUrl":"https://aoctrl.com/api/mcp/products/A9D61806","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, residual current breaker with overcurrent protection, 1P + Ns, 6 A rated, C-curve, 30 mA earth leakage, 6 kA breaking capacity, clip-on DIN rail mount.","salesMarkdown":"It integrates a 6 A thermal-magnetic MCB (C-curve) and a 30 mA earth leakage trip into one clip-on DIN rail unit, saving a full module width compared to separate MCB + RCCB. The 6 A rating at 50 °C means it protects a final subcircuit drawing up to that continuous current; the C-curve (magnetic trip at 5–10× In) handles motor and lighting inrush without nuisance tripping. The 30 mA earth leakage sensitivity covers personnel protection (indirect contact) per IEC 61009-1. Breaking capacity is 6 kA Icn at 230/240 V AC — enough for most domestic and light commercial distribution boards, but check the prospective fault current at the point of installation; if it exceeds 6 kA, step up to the iC60H or iC60L variants. Clip-on mount to standard 35 mm DIN rail. The 18 mm width (2 x 9 mm pitches) and 77.5 mm depth fit standard consumer unit and distribution board cutouts. Neutral is on the left (1P + Ns configuration). Tightening torque 3.5 N.m top, 2 N.m bottom. IP20 finger-safe — intended for enclosed panel use only, not washdown environments.","metaTitle":"Schneider Electric A9D61806 Acti9 iC60 RCBO, 6A C-curve, 30m","metaDescription":"Schneider Electric A9D61806 Acti9 iC60 RCBO, 6A rated, C-curve, 30mA earth leakage, 6kA breaking capacity. IEC 61009-1 compliant. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-1 IEC 61009-2-2 AS/NZS 61009.1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Grid distance":"45 mm","Mounting mode":"Clip-on","Surge current":"250 A","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"6000 A Icn at 230/240 V AC 50/60 Hz","Device short name":"iC60N RCBO","Network frequency":"50/60 Hz","Poles description":"1P + Ns","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"6 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"6000 A at 230/240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/au/en/product/A9D61806/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60n-rcbo-1p-+-ns-6a-30ma-a-type-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D61806/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9D61806?","answer":"6 kA Icn at 230/240 V AC, 50/60 Hz. This is the rated short-circuit breaking capacity per IEC 61009-1. For installations with higher prospective fault current, consider the iC60H (10 kA) or iC60L (15 kA) variants in the same footprint."},{"question":"What standards does A9D61806 comply with?","answer":"IEC 61009-1, IEC 61009-2-2, and AS/NZS 61009.1. These cover the requirements for RCBOs — combined overcurrent and residual current protection — for household and similar installations."},{"question":"What is the earth leakage sensitivity of A9D61806?","answer":"30 mA, integrated into the unit. This provides personnel protection against indirect contact and is the standard sensitivity for final circuits in most residential and light commercial applications."},{"question":"Where can I buy A9D61806 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D61806","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D61806 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}