{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D62616","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D62616","canonicalUrl":"https://aoctrl.com/schneider/A9D62616","factsUrl":"https://aoctrl.com/api/mcp/products/A9D62616","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi RCBO, 1P+N, 16 A rated, C-curve, 30 mA earth-leakage sensitivity, 6 kA breaking capacity, clip-on DIN rail mount.","salesMarkdown":"It combines a 16 A thermal-magnetic trip unit (C-curve, magnetic trip 5–10 × In) with integrated 30 mA earth-leakage protection in a single 36 mm wide module that clips onto DIN rail. The 16 A rated current with C-curve characteristic means the unit holds steady-state loads up to 16 A and trips instantaneously on faults between 5 and 10 times rated current (80–160 A). This suits mixed resistive-inductive loads — lighting banks, small motor circuits, socket-outlet groups — where inrush is moderate but not purely resistive. ## Panel integration Terminals accept 1–16 mm² rigid or 1–10 mm² flexible conductors; wire stripping length is 15 mm and tightening torque is 2 N·m. IP20 on the body, IP40 inside a modular enclosure. Limitation class 3 for energy let-through. Electrical and mechanical durability rated at 20,000 cycles each.","metaTitle":"Schneider Electric A9D62616 Acti9 iDPN Vigi, 16 A C-curve RC","metaDescription":"Schneider Electric A9D62616 Acti9 iDPN Vigi RCBO, 16 A rated, C-curve, 30 mA earth leakage, 6 kA breaking capacity. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type AC-G","[Ue] rated operational voltage":"220...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Delayed","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9D62616/acti9-idpn-n-vigi-rcbo-1p+n-16a-c-curve-6000a-30ma-type-acg/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D62616/alternatives.json"},"ai":{"faq":[{"question":"What is the A9D62616 used for?","answer":"It is a 1P+N residual-current circuit breaker with overcurrent protection rated 16 A, C-curve, 30 mA earth leakage, for distribution boards in residential and light commercial installations."},{"question":"Where can I buy the A9D62616?","answer":"The A9D62616 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to the A9D62616 in the Acti9 range?","answer":"Within the Acti9 iDPN Vigi family, the closest alternative differs by rated current or earth-leakage sensitivity — for example, a 10 A or 20 A variant, or a 300 mA sensitivity version. No pin-compatible direct substitute is listed as an official replacement."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D62616","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D62616 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}