{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D64810","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D64810","canonicalUrl":"https://aoctrl.com/schneider/A9D64810","factsUrl":"https://aoctrl.com/api/mcp/products/A9D64810","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, 1P+N, 10 A, C-curve, 30 mA earth-leakage sensitivity, 6000 A Icn at 240 V AC, DIN-rail clip-on, white.","salesMarkdown":"It protects a single-phase final subcircuit against both overload/short-circuit (thermal-magnetic trip, C-curve) and earth leakage (30 mA sensitivity). The 10 A rated current at 50 °C means it is sized for lighting or general-purpose socket circuits drawing up to 10 A continuous; the C-curve means magnetic trip occurs at 5 to 10 times In, so it tolerates moderate inrush from small motors or capacitive loads without nuisance tripping. The 30 mA earth-leakage threshold provides personal protection against indirect contact in TN earthing systems. Breaking capacity is 6000 A Icn at 240 V AC 50/60 Hz — sufficient for most residential and light commercial distribution boards where the prospective short-circuit current stays below 6 kA. Clip-on DIN-rail mount — no screws needed. Terminals are screw-clamp: top accepts 1…25 mm² rigid or 1…16 mm² flexible; bottom accepts 1…16 mm² rigid or 1…10 mm² flexible. Wire stripping length is 14 mm for top connection, 13 mm for bottom. The device is padlockable with a Ø 4 mm padlock for lockout/tagout. Certified to IEC 61009-1 and IEC 61009-2-2 — the international standard for RCBOs. The part carries limitation class 3, meaning it limits let-through energy under short-circuit conditions. Electrical durability is rated at 5000 cycles, mechanical durability at 20000 cycles. The device is suitable for isolation — it provides a visible break when toggled OFF.","metaTitle":"A9D64810 Acti9 iC60 RCBO, 10 A, C-curve, 30 mA, 6 kA","metaDescription":"A9D64810 Acti9 iC60 RCBO by Schneider Electric. 1P+N, 10 A, C-curve, 30 mA earth leakage, 6 kA breaking capacity. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-2-2 IEC 61009-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Grid distance":"45 mm","Mounting mode":"Clip-on","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"6000 A Icn at 240 V AC 50/60 Hz","Device short name":"iC60N RCBO","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"10 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"6000 A at 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9D64810/ic60n-earth-leakage-circuit-breaker-1p-+-n-c-curve-10-a-30-ma-240-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D64810/alternatives.json"},"ai":{"faq":[{"question":"What is A9D64810's listed depth (77.5 mm) on this component line?","answer":"The A9D64810 has a depth of 77.5 mm, height of 110 mm, and width of 18 mm. It occupies 2 x 9 mm DIN-rail pitches."},{"question":"What compliance documentation does this brand provide for A9D64810 (RoHS, REACH, UL, IEC)?","answer":"The device is certified to IEC 61009-1 and IEC 61009-2-2. It is suitable for isolation per IEC standards. RoHS and REACH declarations are typically available from Schneider Electric's documentation portal for the Acti9 range; the evidence does not list UL or CSA marks."},{"question":"Where can I buy A9D64810 and what is the lead time?","answer":"The A9D64810 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no firm stock count or lead-time figure is published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D64810","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D64810 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}