{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D68604","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D68604","canonicalUrl":"https://aoctrl.com/schneider/A9D68604","factsUrl":"https://aoctrl.com/api/mcp/products/A9D68604","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi RCBO, A9D68604, 1P+N, 4 A, B curve, 6 kA breaking capacity, 300 mA earth leakage, DIN rail.","salesMarkdown":"It protects a single-phase final subcircuit (1P+N) at 4 A rated current, B curve, with integrated 300 mA earth-leakage protection. Breaking capacity is 6 kA Icn at 230/240 V AC, 50 Hz, per EN/IEC 61009-2-1. The 4 A rating and B curve (magnetic trip at 3–5× In, so 12–20 A) make this unit suited for lighting circuits or small resistive loads where inrush is low. The integrated 300 mA residual-current element is a delayed or S-type characteristic by default — it's intended for fire protection or circuits where a 30 mA RCD would nuisance-trip (e.g. fixed equipment with natural leakage). Not for socket-outlet circuits requiring 30 mA personal protection. Neutral is on the left, phase on the right. The 36 mm width and clip-on DIN rail mount mean it snaps directly into a standard distribution board alongside other Acti9 or third-party modular devices. The toggle indicates ON, OFF, and fault-trip status locally.","metaTitle":"Schneider Electric A9D68604 Acti9 iDPN Vigi RCBO, 4 A, B Cur","metaDescription":"Schneider Electric A9D68604 Acti9 iDPN Vigi RCBO. 4 A rated, B curve, 6 kA breaking capacity, 300 mA earth leakage. DIN rail mount, current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"4 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"220...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/sg/en/product/A9D68604/acti9-idpn-n-vigi-rcbo-1p+n-4a-b-curve-6000a-300ma-type-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D68604/alternatives.json"},"ai":{"faq":[{"question":"What is the A9D68604 used for?","answer":"It is a combined RCBO (residual current breaker with overcurrent protection) for a 1P+N final subcircuit. The 4 A B curve and 300 mA earth leakage suit lighting or fixed equipment circuits where personal protection (30 mA) is not required."},{"question":"Where can I buy the A9D68604?","answer":"The A9D68604 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quotation."},{"question":"What is the breaking capacity of the A9D68604?","answer":"The breaking capacity is 6 kA Icn at 220–240 V AC, 50 Hz, conforming to EN/IEC 61009-2-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D68604","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D68604 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}