{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D68640","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D68640","canonicalUrl":"https://aoctrl.com/schneider/A9D68640","factsUrl":"https://aoctrl.com/api/mcp/products/A9D68640","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi, RCBO, 40 A, 6 kA, 300 mA, Curve B, 1P+N, 50 Hz, DIN rail.","salesMarkdown":"It carries a 40 A rated current (In) and a 6000 A Icn breaking capacity at 220...240 V AC, 50 Hz, compliant with EN/IEC 61009-2-1. The integrated earth-leakage protection trips at 300 mA, so it covers ground-fault protection for final circuits where a 30 mA sensitivity would cause nuisance trips on longer cable runs or equipment with natural leakage. Clip-on mounting to DIN rail, 36 mm width — four 9 mm pitches. IP20 on the device body, IP40 inside a modular enclosure — fine for distribution boards and residential/commercial consumer units. Curve B means magnetic trip between 3 and 5 times In — 120 to 200 A instantaneously. That suits resistive loads and short cable runs where inrush is low; for motor or transformer circuits with higher starting surges, a Curve C or D would be the better call. The 300 mA residual sensitivity is sized for distribution sub-mains or socket-outlet circuits where 30 mA RCDs would nuisance-trip from cable capacitance or equipment leakage.","metaTitle":"Schneider Electric A9D68640 Acti9 iDPN Vigi RCBO, 40 A, 6 kA","metaDescription":"Schneider Electric A9D68640 Acti9 iDPN Vigi RCBO, 40 A rated, 6 kA breaking capacity, 300 mA earth leakage, Curve B, 1P+N, 50 Hz, active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"40 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"220...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9D68640/acti9-idpn-n-vigi-rcbo-1p+n-40a-b-curve-6000a-300ma-type-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D68640/alternatives.json"},"ai":{"faq":[{"question":"What is A9D68640 used for?","answer":"It is a 1P+N RCBO (overcurrent + earth leakage) for distribution final circuits, rated 40 A, 6 kA breaking capacity, with 300 mA residual protection. Typical use: sub-main or socket-outlet protection in residential or commercial distribution boards."},{"question":"Where can I buy A9D68640?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"What is the difference between A9D68640 and a standard MCB?","answer":"A standard MCB provides only overcurrent protection (thermal-magnetic). The A9D68640 adds integrated earth-leakage protection at 300 mA, so it covers both overcurrent and residual-current faults in one DIN-rail module."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D68640","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D68640 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}