{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D87425","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D87425","canonicalUrl":"https://aoctrl.com/schneider/A9D87425","factsUrl":"https://aoctrl.com/api/mcp/products/A9D87425","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, 4P, 25 A, curve B, 30 mA earth-leakage sensitivity, 6 kA breaking capacity, DIN-rail mount, white.","salesMarkdown":"The A9D87425 is a 4-pole Acti9 iC60 RCBO (residual-current circuit breaker with overcurrent protection) rated 25 A with a B curve — magnetic tripping between 3 and 5 times In, so it clears short-circuit faults quickly on resistive or general-purpose loads without nuisance trips from inrush. The 30 mA earth-leakage sensitivity provides personnel protection against direct contact, meeting the standard for socket-outlet circuits in residential and commercial distribution boards. Breaking capacity is 6 kA Icu at 380–415 V AC 50 Hz per EN/IEC 60947-2, which means it safely interrupts a fault current up to that level without welding contacts or cascading upstream — sized for most sub-distribution panels where the prospective short-circuit current stays under 6 kA. The thermal-magnetic trip unit combines a bimetal strip for overload protection (time-delayed) and a solenoid for short-circuit protection (instantaneous). The B curve holds the magnetic trip threshold at 3–5× In, so a 25 A unit trips magnetically between 75 A and 125 A — a good match for lighting, socket outlets, and control circuits where the load doesn't draw a heavy starting surge. Clip-on mounting onto a DIN rail — 8 pitches of 9 mm between poles, so the 4-pole unit occupies 72 mm of rail width. Height is 86 mm, depth 78 mm. Local signalling on the toggle shows ON, OFF, and fault-trip positions — no need to guess whether the device tripped on overcurrent or earth leakage. The fault-trip indication is mechanical, so it works even without auxiliary contacts.","metaTitle":"Schneider Electric A9D87425 Acti9 iC60 RCBO, 25 A, 4P, 30 mA","metaDescription":"Schneider Electric A9D87425 Acti9 iC60 RCBO, 25 A rated current, 4 poles, 30 mA earth-leakage sensitivity, curve B. 6 kA breaking capacity. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"78 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"86 mm","Standards":"EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"250 A","Quality labels":"KEMA-KEUR VDE IMQ NF","Tropicalisation":"2","lifecycle_stage":"current","Connection pitch":"9 mm between poles","Limitation class":"1 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iC60 RCBO","Network frequency":"50 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"4","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"No conforming to IEC 60947-1","Contact position indicator":"No","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"380...415 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA 100 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES Bottom: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9D87425/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60-4p-25a-b-curve-6000a-6ka-a-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D87425/alternatives.json"},"ai":{"faq":[{"question":"What is A9D87425's breaking capacity?","answer":"The breaking capacity is 6 kA Icu at 380–415 V AC 50 Hz conforming to EN/IEC 60947-2, and 6000 A Icn at the same voltage conforming to EN/IEC 61009-2-1."},{"question":"What compliance documentation does Schneider provide for A9D87425?","answer":"The device carries KEMA-KEUR, VDE, IMQ, and NF quality labels, and complies with EN/IEC 60947-2 and EN/IEC 61009-2-1 standards. Overvoltage category III per IEC 60364."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D87425","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D87425 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}