{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D97425","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D97425","canonicalUrl":"https://aoctrl.com/schneider/A9D97425","factsUrl":"https://aoctrl.com/api/mcp/products/A9D97425","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, A9D97425, 4P, 25 A rated, 30 mA earth leakage, B-curve, 6 kA Icu, clip-on DIN rail.","salesMarkdown":"The A9D97425 is a Schneider Electric Acti9 iC60 RCBO — a combined residual-current circuit breaker with overcurrent protection, in a 4-pole (4P) configuration. It carries a 25 A rated current (In) with a B-curve magnetic trip threshold of 3...5 x In, meaning it trips instantaneously on short-circuit currents between 75 A and 125 A — suited for protecting general-purpose circuits with moderate inrush, like lighting or socket outlets. The integrated earth-leakage protection is set to 30 mA sensitivity, covering personnel protection (additional shock-risk mitigation) per IEC standards. Breaking capacity is 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2, and 6 kA Icn per EN/IEC 61009-2-1 — adequate for most distribution outgoing circuits in residential and light commercial panels. Clip-on mounting to DIN rail (EN/IEC 60715) — 9 mm pole pitch, 8 pitches wide (72 mm width, 86 mm height, 78 mm depth). IP40 in distribution enclosure, IP20 on the terminals. Toggle control with local ON/OFF/fault-trip indication. Fits standard Acti9 distribution boards and enclosures.","metaTitle":"Schneider Electric A9D97425 Acti9 iC60 RCBO, 25 A, 30 mA, B-","metaDescription":"Schneider Electric A9D97425 Acti9 iC60 RCBO, 25 A rated, 30 mA earth leakage, B-curve, 4-pole, 6 kA breaking capacity. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"78 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"86 mm","Standards":"EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"3000 A","Quality labels":"IMQ KEMA-KEUR VDE NF","Tropicalisation":"2","lifecycle_stage":"current","Connection pitch":"9 mm between poles","Limitation class":"1 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iC60 RCBO","Network frequency":"50 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"4","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"No conforming to IEC 60947-1","Contact position indicator":"No","Electromagnetic compatibility":"8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"380...415 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA 100 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES Bottom: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9D97425/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60-4p-25a-b-curve-6000a-6ka-asi-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D97425/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D97425 and what is the lead time?","answer":"The A9D97425 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of A9D97425?","answer":"25 A rated current, 30 mA earth-leakage sensitivity, B-curve (3...5 x In magnetic trip), 6 kA Icu breaking capacity at 380...415 V AC, 4 poles."},{"question":"What compliance documentation does Schneider provide for A9D97425?","answer":"The part carries IMQ, KEMA-KEUR, VDE, and NF quality labels, and conforms to EN/IEC 60947-2 and EN/IEC 61009-2-1. Standard RoHS/REACH documentation is available from Schneider Electric."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D97425","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D97425 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}