{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DC4713","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DC4713","canonicalUrl":"https://aoctrl.com/schneider/A9DC4713","factsUrl":"https://aoctrl.com/api/mcp/products/A9DC4713","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40H RCBO, A9DC4713, 3P+N, 13 A, 30 mA, curve C, 10 kA Icn at 400 V AC.","salesMarkdown":"It combines a 13 A thermal-magnetic trip (curve C, magnetic trip 5–10 × In) with integrated 30 mA earth-leakage protection in a single DIN-rail module. Rated breaking capacity is 10 kA Icn at 400 V AC, 50/60 Hz, per EN/IEC 61009-2-1, which covers the majority of commercial and light industrial distribution boards where the prospective fault current stays under that threshold. This is a current-production part (lifecycle stage: current) from the Acti9 range, designed for outgoing feeder protection in AC networks. The 13 A rated current (In) and curve C (5–10 × In magnetic trip) mean this RCBO is sized for general-purpose circuits feeding socket outlets, lighting, or small loads where moderate inrush is expected — not for motor starting or heavy inductive loads that would need a D curve. The 30 mA earth-leakage sensitivity provides additional protection against electric shock in circuits where the standard is required (e.g., socket circuits in many IEC countries). For panels with a higher prospective short-circuit current, upstream current-limiting devices or a higher-rated breaker would be needed. IP20 on the device body, IP40 in a modular enclosure — fine for dry indoor panels, not for washdown environments. ## Installation and wiring notes Clip-on DIN-rail mount, neutral on the left. Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible cable; tighten to 2 N·m. Strip 14 mm. The 18 mm phase-to-phase pitch and 9 mm phase-to-neutral pitch are standard for the Acti9 range — busbars and comb connectors fit directly. Local signalling shows fault indication and ON/OFF status on the toggle. Electrical and mechanical durability are both rated at 20,000 cycles — adequate for normal switching duty in a distribution board; not intended for frequent manual switching as a disconnect.","metaTitle":"Schneider Electric A9DC4713 Acti9 iCV40 RCBO, 13 A, 30 mA, 1","metaDescription":"Schneider Electric A9DC4713 Acti9 iCV40H RCBO, 13 A rated, 30 mA earth leakage, curve C, 10 kA breaking capacity. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"90 mm","Colour":"White","Height":"93 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"10","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40","Mounting mode":"Clip-on","lifecycle_stage":"current","Connection pitch":"18 mm between phases 9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"Fault indication ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40H","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"13 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"3","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device Sealable","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-1","[Ui] rated insulation voltage":"440 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"400 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 3000 A at 400 V AC 50/60 Hz conforming to EN 61009-2-1 Idm 500 A at 400 V AC 50/60 Hz conforming to IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: tooth"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/il/en/product/A9DC4713/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-icv40-3p+n-13-a-c-curve-10000-a-30-ma-a-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DC4713/alternatives.json"},"ai":{"faq":[{"question":"What is A9DC4713's listed range (Acti9) on this component line?","answer":"It belongs to the Schneider Electric Acti9 range, specifically the iCV40H series of RCBOs."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DC4713","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DC4713 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}