{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DC4716","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DC4716","canonicalUrl":"https://aoctrl.com/schneider/A9DC4716","factsUrl":"https://aoctrl.com/api/mcp/products/A9DC4716","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40H RCBO, A9DC4716, 3P+N, 16 A, 30 mA, C-curve, 10 kA Icn at 400 V AC, thermal-magnetic trip, integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric A9DC4716 is an Acti9 iCV40H RCBO — a combined residual-current circuit breaker with overcurrent protection, in a 3P+N, 4-module-wide (90 mm) clip-on DIN-rail housing. It integrates a 16 A thermal-magnetic overcurrent trip (C-curve, 5–10 x In magnetic threshold) with a 30 mA earth-leakage sensor on the same outgoing circuit, so a single device covers both short-circuit and ground-fault protection on a three-phase distribution outgoer. Rated 10 kA Icn at 400 V AC 50/60 Hz per EN/IEC 61009-2-1, limitation class 3, meaning it clips the let-through energy on a fault — downstream equipment sees less thermal stress than with a class-1 or class-2 device. Clip-on to DIN rail (EN/IEC 60715). 9 mm pitch between phase and neutral, 18 mm between phases — the 4-module body (90 mm wide) occupies ten 9 mm pitches. Neutral on the left. Tunnel terminals top and bottom accept 1–16 mm² rigid or 1–10 mm² flexible; strip 14 mm, torque to 2 N·m. The 73 mm depth leaves clearance for standard gland plates and enclosure backwalls.","metaTitle":"Schneider Electric A9DC4716 Acti9 iCV40H RCBO, 16 A, 30 mA,","metaDescription":"Schneider Electric A9DC4716 Acti9 iCV40H RCBO, 16 A rated current, 30 mA earth leakage, C-curve, 10 kA breaking capacity at 400 V AC. EN/IEC 61009-2-1. Sourced to order. Request qu","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"90 mm","Colour":"White","Height":"93 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"10","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40","Mounting mode":"Clip-on","lifecycle_stage":"current","Connection pitch":"18 mm between phases 9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON/OFF indication Fault indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40H","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"16 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"3","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Sealable Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-1","[Ui] rated insulation voltage":"440 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"400 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 3000 A at 400 V AC 50/60 Hz conforming to EN 61009-2-1 Idm 500 A at 400 V AC 50/60 Hz conforming to IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: tooth"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$223.07","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/il/en/product/A9DC4716/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-icv40-3p+n-16-a-c-curve-10000-a-30-ma-a-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DC4716/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9DC4716?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time; the part is sourced to order through independent distribution channels."},{"question":"What is A9DC4716's listed depth (73 mm) on this component line?","answer":"The A9DC4716 has a depth of 73 mm, which is the dimension from the DIN-rail mounting face to the front of the toggle. This is standard for a 4-module Acti9 RCBO and fits most 100 mm-deep enclosures with clearance for wiring."},{"question":"What is A9DC4716's listed range (Acti9) on this component line?","answer":"The A9DC4716 belongs to the Schneider Electric Acti9 range, specifically the iCV40H series of combined RCBOs. Acti9 is Schneider's modular DIN-rail distribution platform for residential and commercial final circuits."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DC4716","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DC4716 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}