{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DC6910","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DC6910","canonicalUrl":"https://aoctrl.com/schneider/A9DC6910","factsUrl":"https://aoctrl.com/api/mcp/products/A9DC6910","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, A9DC6910, 3P + Ns, 10 A rated current, C-curve, 30 mA earth-leakage sensitivity, 6000 A Icn at 400/415 V, clip-on DIN-rail mount, IP20.","salesMarkdown":"It combines a 10 A thermal-magnetic circuit breaker (C-curve) with integrated 30 mA earth-leakage protection in a single 54 mm wide module that clips onto a DIN rail. The 10 A rated current (at 30 °C) and C-curve trip characteristic make this RCBO suited for general-purpose circuits with moderate inrush — lighting banks, small motor loads, or socket outlets where the starting surge is higher than a B-curve would tolerate. The 30 mA earth-leakage sensitivity provides personal protection against indirect contact, complying with AS/NZS 61009.1. The 6000 A Icn at 400/415 V is the short-circuit breaking capacity under standard conditions; limitation class 3 means it limits let-through energy during a fault, reducing stress on downstream wiring. The device occupies 6 x 9 mm pitches (54 mm) on a DIN rail, with a depth of 77.2 mm and height of 112 mm. The screw-clamp terminals accept 1 to 25 mm² rigid cable; strip length is 11 mm for the bottom connection and tighten to 2.5 N.m.","metaTitle":"A9DC6910 Acti9 iC60 RCBO, 10 A, C-curve, 30 mA, 6 kA","metaDescription":"Schneider Electric A9DC6910 Acti9 iC60 RCBO, 10 A rated current, C-curve, 30 mA earth leakage, 6 kA breaking capacity at 400/415 V. Current lifecycle stage. Available to order agai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.2 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"112 mm","Standards":"AS/NZS 61009.1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Grid distance":"45 mm","Mounting mode":"Clip-on","Surge current":"250 A","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"6000 A Icn at 400/415 V","Device short name":"iC60N3 RCBO","Network frequency":"50/60 Hz","Poles description":"3P + Ns","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2.5 N.m top","[In] rated current":"10 A at 30 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 11 mm for bottom connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"3","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to IEC 61009-1","Circuit breaker application":"Distribution","Locking options description":"Handle sealable with cable diameter 1.4mm in OFF or ON position","Test button operating voltage":"260...457 V","[Ui] rated insulation voltage":"500 V","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"400/415 V","Ambient air temperature for storage":"-25...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"6000 A","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"YES","Operating voltage for protection against earth-leakage":"150...457 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/au/en/product/A9DC6910/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60-rcbo-3p+ns-c-curve-10a-30ma-a-type-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DC6910/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9DC6910?","answer":"The A9DC6910 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of A9DC6910?","answer":"The breaking capacity is 6000 A Icn at 400/415 V AC, with limitation class 3."},{"question":"What earth-leakage sensitivity does A9DC6910 provide?","answer":"The integrated earth-leakage protection is rated at 30 mA sensitivity."},{"question":"What compliance standards does A9DC6910 meet?","answer":"It complies with AS/NZS 61009.1 for residual current breakers with overcurrent protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DC6910","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DC6910 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}