{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DC6932","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DC6932","canonicalUrl":"https://aoctrl.com/schneider/A9DC6932","factsUrl":"https://aoctrl.com/api/mcp/products/A9DC6932","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, 3P + Ns, 32 A rated current, C-curve, 30 mA earth-leakage sensitivity, 6000 A breaking capacity at 400/415 V, clip-on DIN rail mount.","salesMarkdown":"It combines thermal-magnetic overcurrent protection with integrated 30 mA earth-leakage detection in a single DIN-rail module, saving panel space over separate MCB and RCCB units. The limitation class 3 rating means it restricts let-through energy well, aiding downstream coordination. Earth-leakage sensitivity is 30 mA — the standard for personnel protection in residential and commercial circuits per AS/NZS 61009.1. The integrated earth-leakage function eliminates the need for a separate RCCB, reducing wiring and panel depth. Clip-on mounting to a 45 mm grid DIN rail. The 54 mm width (6 x 9 mm pitches) fits standard distribution board cutouts. Neutral is factory-fixed on the left; padlockable with a 4 mm diameter padlock for lockout/tagout during maintenance. Tightening torque is 2.5 N.m on the power circuit top connection; strip length is 11 mm for bottom connection. IP20 rated for installation within an enclosure.","metaTitle":"Schneider Electric A9DC6932 Acti9 iC60 RCBO, 32 A, C-curve,","metaDescription":"Schneider Electric A9DC6932 Acti9 iC60 RCBO, 32 A rated current, C-curve, 30 mA earth leakage, 6000 A breaking capacity at 400/415 V. Active production. Available to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.2 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"112 mm","Standards":"AS/NZS 61009.1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Grid distance":"45 mm","Mounting mode":"Clip-on","Surge current":"250 A","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"6000 A Icn at 400/415 V","Device short name":"iC60N3 RCBO","Network frequency":"50/60 Hz","Poles description":"3P + Ns","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2.5 N.m top","[In] rated current":"32 A at 30 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 11 mm for bottom connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"3","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to IEC 61009-1","Circuit breaker application":"Distribution","Locking options description":"Handle sealable with cable diameter 1.4mm in OFF or ON position","Test button operating voltage":"260...457 V","[Ui] rated insulation voltage":"500 V","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"400/415 V","Ambient air temperature for storage":"-25...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"6000 A","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"YES","Operating voltage for protection against earth-leakage":"150...457 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/au/en/product/A9DC6932/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60-rcbo-3p+ns-c-curve-32a-30ma-a-type-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DC6932/alternatives.json"},"ai":{"faq":[{"question":"What is the A9DC6932's breaking capacity?","answer":"The breaking capacity is 6000 A Icn at 400/415 V AC, suitable for standard commercial and light industrial distribution boards."},{"question":"What compliance documentation does Schneider Electric provide for the A9DC6932?","answer":"The A9DC6932 is certified to AS/NZS 61009.1, covering residual current and overcurrent protection requirements for Australian and New Zealand installations."},{"question":"What is the earth-leakage sensitivity of the A9DC6932?","answer":"The earth-leakage sensitivity is 30 mA, the standard level for personnel protection."},{"question":"Where can I buy the A9DC6932?","answer":"The A9DC6932 is available to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DC6932","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DC6932 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}