{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DE3716","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DE3716","canonicalUrl":"https://aoctrl.com/schneider/A9DE3716","factsUrl":"https://aoctrl.com/api/mcp/products/A9DE3716","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40 series RCBO, order code A9DE3716, 16 A rated, 30 mA earth-leakage sensitivity, C-curve, 6 kA breaking capacity at 400 V AC, 3P+N, DIN rail mount.","salesMarkdown":"The Schneider Electric A9DE3716 is an Acti9 iCV40 residual-current circuit breaker with overcurrent protection (RCBO), combining a 16 A thermal-magnetic trip unit (curve C, magnetic tripping between 5 and 10 times In) with an integrated 30 mA earth-leakage sensor in a single 3P+N module. The RCBO clips onto a DIN rail (mounting support: DIN rail, clip-on) and occupies 10 x 9 mm pitches — 90 mm width — with the neutral on the left. The tunnel-type terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible conductors; tightening torque is 2 N.m top or bottom. The IP20 rating on the body (IP40 in a modular enclosure) means it is suitable for installation inside a distribution board that provides the final enclosure seal. ## Deployment context This RCBO is intended as an outgoer device in a distribution board (device location in system: outgoer; device application: distribution). The 30 mA earth-leakage protection is mandatory in many national wiring codes for circuits supplying socket outlets and portable equipment. The pollution degree 3 rating and overvoltage category III (IEC 60364) confirm it is designed for fixed installation in a building's main or sub-distribution board, not for outdoor or wet-location mounting without additional enclosure protection.","metaTitle":"Schneider Electric A9DE3716 Acti9 iCV40 RCBO, 16 A, 30 mA, 6","metaDescription":"Schneider Electric A9DE3716 Acti9 iCV40 RCBO, 16 A rated, 30 mA earth-leakage, 6 kA breaking capacity at 400 V AC, C-curve, 3P+N, DIN rail. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"90 mm","Colour":"White","Height":"93 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"10","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40","Mounting mode":"Clip-on","Quality labels":"EAC IMQ","lifecycle_stage":"current","Connection pitch":"18 mm between phases 9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"Fault indication ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"16 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"3","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device Sealable","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-1","[Ui] rated insulation voltage":"440 V AC 50/60 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"400 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 3000 A at 400 V AC 50/60 Hz conforming to EN 61009-2-1 Idm 500 A at 400 V AC 50/60 Hz conforming to IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: tooth"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$87.62","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/hk/en/product/A9DE3716/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-icv40n-3p+n-16a-c-curve-6000a-ac-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DE3716/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9DE3716 and how do I get a price?","answer":"The A9DE3716 is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing — stock levels and lead time are confirmed at quote time."},{"question":"What is A9DE3716's listed depth (73 mm) on this component line?","answer":"The A9DE3716 has a depth of 73 mm, with a width of 90 mm and height of 93 mm. These dimensions fit standard modular distribution board spacing."},{"question":"What compliance documentation does this brand provide for A9DE3716 (RoHS, REACH, UL, IEC)?","answer":"The A9DE3716 is designed to EN/IEC 61009-2-1 (standard for RCBOs) and carries quality labels EAC and IMQ. It is rated for pollution degree 3 and overvoltage category III per IEC 60364. RoHS/REACH compliance documentation is typically available from Schneider Electric upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DE3716","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DE3716 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}