{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DF7620","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DF7620","canonicalUrl":"https://aoctrl.com/schneider/A9DF7620","factsUrl":"https://aoctrl.com/api/mcp/products/A9DF7620","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40 RCBO, 1P+N, 20 A, C-curve, 6 kA Icn at 230 V AC, 300 mA earth-leakage sensitivity, DIN-rail clip-on, white.","salesMarkdown":"The A9DF7620 is an Acti9 iCV40N residual-current circuit breaker (RCBO) combining overcurrent and earth-leakage protection in a single 1P+N module. The integrated 300 mA earth-leakage protection covers the whole outgoing circuit, meeting the basic fire-prevention and personnel-protection requirement for socket and lighting final circuits in most IEC-based installations. Clip-on mounting to a standard 35 mm DIN rail and a 36 mm width (4 x 9 mm pitches) mean it fits directly into a modular consumer unit or distribution board alongside other Acti9 devices. The IP20 finger-safe enclosure is rated for dry indoor panels; the modular enclosure achieves IP40 when installed in a board with a matching cover. Limitation class 3 (energy-limiting) means the device restricts let-through energy during a short-circuit, reducing stress on downstream wiring and connected equipment. Quality labels include EAC (Eurasian Customs Union) and VDE (German independent certification). Operating altitude is rated to 2000 m without derating.","metaTitle":"Schneider Electric A9DF7620 Acti9 iCV40 RCBO, 20 A C-curve,","metaDescription":"Schneider Electric A9DF7620 Acti9 iCV40 RCBO, 20 A rated, C-curve, 6 kA breaking capacity at 230 V AC, 300 mA earth leakage. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40","Mounting mode":"Clip-on","Quality labels":"EAC VDE","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON/OFF indication Fault indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40N","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"20 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device Sealable","Electromagnetic compatibility":"8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 6000 A at 230 V AC 50/60 Hz conforming to EN 61009-2-1 Idm 500 A at 230 V AC 50/60 Hz conforming to IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: tooth"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9DF7620/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-icv40n-1p+n-20a-c-curve-6000a-asi-type-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DF7620/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for the A9DF7620?","answer":"Pricing and current availability for the A9DF7620 are confirmed at quote time. Submit an RFQ through the storefront to receive a firm quote with lead time."},{"question":"What is the breaking capacity of the A9DF7620?","answer":"The A9DF7620 has a rated breaking capacity (Icn) of 6000 A at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1."},{"question":"What earth-leakage sensitivity does the A9DF7620 provide?","answer":"The integrated earth-leakage protection is set to 300 mA sensitivity, suitable for fire prevention and basic personnel protection on final circuits."},{"question":"What standards does the A9DF7620 comply with?","answer":"The A9DF7620 is designed and certified to EN/IEC 61009-2-1, the standard for residual-current circuit breakers with overcurrent protection. It also carries EAC and VDE quality labels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DF7620","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DF7620 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}