{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DF7625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DF7625","canonicalUrl":"https://aoctrl.com/schneider/A9DF7625","factsUrl":"https://aoctrl.com/api/mcp/products/A9DF7625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40 RCBO, A9DF7625, 25 A rated, C-curve, 6000 A breaking capacity, 300 mA earth-leakage, 1P+N, DIN-rail mount.","salesMarkdown":"The integrated earth-leakage protection trips at 300 mA, covering the whole outgoing circuit against ground faults. Clip-on mounting to a standard DIN rail. The 36 mm width and 85 mm height match the Acti9 modular enclosure footprint. 4 x 9 mm pitches for the phase-to-neutral connection. Neutral is on the left. Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible; tighten to 2 N·m. Wire stripping length 14 mm. IP20 body, IP40 in a modular enclosure — fine for a clean indoor distribution board, not for washdown areas.","metaTitle":"Schneider Electric A9DF7625 Acti9 iCV40 25A RCBO, 6000A, C-C","metaDescription":"Schneider Electric A9DF7625 Acti9 iCV40 25A RCBO with integrated 300mA earth-leakage protection. 6000A breaking capacity, C-curve, DIN-rail mount. Active production. Request a quot","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40","Mounting mode":"Clip-on","Quality labels":"VDE EAC","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"Fault indication ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40N","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"25 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Sealable Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 6000 A at 230 V AC 50/60 Hz conforming to EN 61009-2-1 Idm 500 A at 230 V AC 50/60 Hz conforming to IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: tooth"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9DF7625/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-icv40n-1p+n-25a-c-curve-6000a-asi-type-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DF7625/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9DF7625?","answer":"6000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1. That is the rated short-circuit capacity for this RCBO."},{"question":"What earth-leakage sensitivity does A9DF7625 have?","answer":"Integrated earth-leakage protection with 300 mA sensitivity. Suitable for general-purpose ground-fault protection on outgoing circuits."},{"question":"What standards does A9DF7625 comply with?","answer":"Compliant with EN/IEC 61009-2-1, the RCBO product standard. Also carries VDE and EAC quality labels. Overvoltage category III per IEC 60364."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DF7625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DF7625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}