{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DF8616","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DF8616","canonicalUrl":"https://aoctrl.com/schneider/A9DF8616","factsUrl":"https://aoctrl.com/api/mcp/products/A9DF8616","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40H RCBO, 1P+N, 16 A rated, C-curve, 10 kA breaking capacity, 300 mA earth-leakage sensitivity, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The 300 mA earth-leakage sensitivity is a fixed sensitivity — suitable for circuits where nuisance tripping from leakage in long cable runs or equipment filters must be avoided, but not for personal shock protection (which requires 30 mA or lower). The thermal-magnetic trip unit gives a standard inverse-time characteristic for overloads and instantaneous magnetic release for shorts. The C-curve is the most common for general-purpose distribution in Europe and Asia — it holds up to 5–10 × In before the magnetic element trips, which avoids nuisance trips on moderate motor or transformer inrush while still clearing hard faults quickly. ## Deployment context The tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible, with a tightening torque of 2 N·m and a strip length of 14 mm. The 85 mm height and 73 mm depth fit standard modular enclosure cutouts.","metaTitle":"Schneider Electric A9DF8616 Acti9 iCV40H RCBO, 16 A, 10 kA,","metaDescription":"Schneider Electric A9DF8616 Acti9 iCV40H RCBO, 16 A rated, 10 kA breaking capacity, 300 mA earth leakage, C-curve, 1P+N, DIN rail mount. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40","Mounting mode":"Clip-on","Quality labels":"EAC VDE","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"Fault indication ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"16 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Sealable Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 6000 A at 230 V AC 50/60 Hz conforming to EN 61009-2-1 Idm 500 A at 230 V AC 50/60 Hz conforming to IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: tooth"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9DF8616/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-icv40h-1p+n-16a-c-curve-10000a-asi-type-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DF8616/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the A9DF8616?","answer":"The breaking capacity is 10,000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1."},{"question":"What earth-leakage sensitivity does the A9DF8616 have?","answer":"The earth-leakage sensitivity is fixed at 300 mA — suitable for circuits where nuisance tripping from leakage in long cable runs or equipment filters must be avoided, but not for personal shock protection."},{"question":"Where can I buy the A9DF8616?","answer":"The A9DF8616 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DF8616","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DF8616 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}