{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DF8625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DF8625","canonicalUrl":"https://aoctrl.com/schneider/A9DF8625","factsUrl":"https://aoctrl.com/api/mcp/products/A9DF8625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40H RCBO, A9DF8625, 25 A rated, C-curve, 10 kA Icn at 230 V AC, integrated 300 mA earth-leakage protection, thermal-magnetic trip, DIN-rail clip-on, 1P+N, 4 modules wide.","salesMarkdown":"The Schneider Electric A9DF8625 is a 25 A RCBO from the Acti9 iCV40H series — a combined overcurrent and residual-current device in a single 36 mm wide (4-module) package. Integrated 300 mA earth-leakage protection covers ground-fault detection in the same unit, saving a DIN slot versus a separate RCCB. Mounts via clip-on to a standard DIN rail (EN 60715). Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; tighten to 2 N·m. Stripping length is 14 mm. Compliance documentation includes VDE and EAC quality labels. The RCBO is designed to EN/IEC 61009-2-1 (residual current operated circuit-breakers with integral overcurrent protection) and carries limitation class 3 for energy-limiting performance under fault conditions. ## Integration into the distribution board Occupies 4 modules (36 mm) on the DIN rail. The IP20 rating applies to the front of the device; IP40 applies when enclosed in a modular enclosure. Operating altitude is limited to 2000 m without derating. Rated for 50/60 Hz AC networks only. The thermal-magnetic trip unit provides both overload (thermal bimetal) and short-circuit (magnetic coil) protection. Electrical and mechanical durability are both rated at 20,000 cycles.","metaTitle":"Schneider Electric A9DF8625 Acti9 iCV40H RCBO, 25 A C-curve,","metaDescription":"Schneider Electric A9DF8625 Acti9 iCV40H RCBO: 25 A, C-curve, 10 kA breaking capacity, integrated 300 mA earth-leakage protection. DIN-rail mount, EN/IEC 61009-2-1. Available to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40","Mounting mode":"Clip-on","Quality labels":"VDE EAC","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"Fault indication ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"25 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Sealable Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 6000 A at 230 V AC 50/60 Hz conforming to EN 61009-2-1 Idm 500 A at 230 V AC 50/60 Hz conforming to IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: tooth"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9DF8625/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-icv40h-1p+n-25a-c-curve-10000a-asi-type-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DF8625/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9DF8625?","answer":"The A9DF8625 has a breaking capacity of 10,000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1."},{"question":"What earth-leakage sensitivity does the A9DF8625 provide?","answer":"Integrated earth-leakage protection with 300 mA sensitivity — suitable for fire protection and general ground-fault detection in distribution circuits."},{"question":"Where can I buy A9DF8625 and what is the lead time?","answer":"The A9DF8625 is sourced to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time; submit an RFQ for a firm lead-time estimate."},{"question":"What compliance standards does A9DF8625 meet?","answer":"The A9DF8625 is designed to EN/IEC 61009-2-1 and carries VDE and EAC quality labels. It is rated limitation class 3 per that standard for energy-limiting performance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DF8625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DF8625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}