{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DG2606","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DG2606","canonicalUrl":"https://aoctrl.com/schneider/A9DG2606","factsUrl":"https://aoctrl.com/api/mcp/products/A9DG2606","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40 RCBO, A9DG2606, 1P+N, 6 A, B-curve, 30 mA earth leakage, 4.5 kA breaking capacity.","salesMarkdown":"## What this RCBO does and why it matters for your panel The Schneider Electric A9DG2606 is an Acti9 iCV40 RCBO — a combined overcurrent and earth-leakage protection device in a 1P+N format, rated 6 A with a B-curve trip characteristic and 30 mA residual-current sensitivity. Breaking capacity is 4500 A Icn at 230 V AC, 50/60 Hz, per EN/IEC 61009-2-1. The limitation class is 3, meaning it limits let-through energy under fault conditions, reducing stress on downstream wiring and equipment. The thermal-magnetic trip unit combines a bimetal strip for overload protection (time-delayed, inversely proportional to current) and a solenoid for short-circuit protection (instantaneous above the magnetic threshold). The magnetic tripping limit of 3–5 x In means for a 6 A device, it trips instantaneously between 18 A and 30 A — typical for B-curve coordination with cable protection. Integrated earth-leakage protection at 30 mA sensitivity covers both sinusoidal AC residual currents (Type AC, implied by the AC network designation) and meets the standard requirement for socket-outlet circuits in many IEC-based wiring regulations. ## Mounting and wiring — what fits where Clip-on mounting to a 35 mm DIN rail, with tunnel-type terminals accepting 1–16 mm² rigid or 1–10 mm² flexible conductors. The 9 mm connection pitch between phase and neutral matches standard Acti9 busbar systems, so it integrates directly into a Schneider distribution board without adaptors.","metaTitle":"Schneider Electric A9DG2606 Acti9 iCV40 6A B-Curve RCBO, 30m","metaDescription":"Schneider Electric A9DG2606 Acti9 iCV40 RCBO, 6A rated, B-curve, 30mA earth leakage, 4.5kA breaking capacity. Current production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40","Mounting mode":"Clip-on","Quality labels":"KEMA-KEUR VDE","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"Fault indication ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"4500 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"6 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device Sealable","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 4500 A at 230 V AC 50/60 Hz conforming to EN 61009-2-1 Idm 500 A at 230 V AC 50/60 Hz conforming to IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"4500 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: tooth"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$202.23","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9DG2606/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-icv40-1p+n-6a-b-curve-4500a-a-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DG2606/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9DG2606?","answer":"4500 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1. This is the rated short-circuit breaking capacity for the device."},{"question":"What does the B-curve mean on this RCBO?","answer":"The B-curve means magnetic tripping occurs at 3 to 5 times the rated current (18–30 A for a 6 A device). It is designed for resistive and light inductive loads where inrush currents are low, such as lighting and socket-outlet circuits."},{"question":"How do I get pricing and availability for A9DG2606?","answer":"Submit an RFQ through this listing. We source and quote this part to order; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DG2606","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DG2606 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}