{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9DG2610","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9DG2610","canonicalUrl":"https://aoctrl.com/schneider/A9DG2610","factsUrl":"https://aoctrl.com/api/mcp/products/A9DG2610","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40 RCBO, A9DG2610, 1P+N, 10 A, B curve, 30 mA earth leakage, 4.5 kA breaking capacity, DIN rail mount.","salesMarkdown":"The integrated 30 mA earth-leakage protection means it covers both overload/short-circuit and ground-fault detection in one DIN-rail unit, saving a module width versus separate MCB + RCD. Breaking capacity is 4.5 kA Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1 — adequate for residential and light commercial sub-distribution boards where the prospective fault current stays under that threshold. Thermal-magnetic trip technology gives a time-delayed thermal response for overloads and an instantaneous magnetic response for shorts. Limitation class 3 means the device limits let-through energy in a fault — relevant for downstream cable protection and coordination with upstream devices. Clip-on mounting to a DIN rail, 36 mm width (4 x 9 mm pitches), 85 mm height, 73 mm depth. Tunnel-type terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; strip length 14 mm, tightening torque 2 N·m. IP20 on the front face, IP40 inside the modular enclosure — standard for distribution boards. Certified to EN/IEC 61009-2-1 with KEMA-KEUR and VDE quality marks. Electrical durability 20,000 cycles, mechanical durability 20,000 cycles. Local signalling provides ON/OFF indication and fault indication on the toggle.","metaTitle":"Schneider Electric A9DG2610 Acti9 iCV40 RCBO, 10A B Curve 30","metaDescription":"Schneider A9DG2610 Acti9 iCV40 RCBO, 10A rated, B curve, 30mA earth leakage, 4.5kA breaking capacity. DIN rail mount, current production, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40","Mounting mode":"Clip-on","Quality labels":"KEMA-KEUR VDE","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON/OFF indication Fault indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"4500 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"10 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device Sealable","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 4500 A at 230 V AC 50/60 Hz conforming to EN 61009-2-1 Idm 500 A at 230 V AC 50/60 Hz conforming to IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"4500 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: tooth"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$202.23","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9DG2610/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-icv40-1p+n-10a-b-curve-4500a-a-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9DG2610/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9DG2610?","answer":"The A9DG2610 has a breaking capacity of 4500 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1."},{"question":"What is the earth-leakage sensitivity of A9DG2610?","answer":"The integrated earth-leakage protection is rated at 30 mA sensitivity."},{"question":"Where can I buy A9DG2610 and how is it quoted?","answer":"The A9DG2610 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9DG2610","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9DG2610 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}