{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F03206","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F03206","canonicalUrl":"https://aoctrl.com/schneider/A9F03206","factsUrl":"https://aoctrl.com/api/mcp/products/A9F03206","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N miniature circuit-breaker, A9F03206, 2P, 6 A, curve B, breaking capacity 36 kA Icu at 12-133 V AC, DIN rail mount.","salesMarkdown":"The A9F03206 is a 2-pole miniature circuit-breaker from the Acti9 iC60N family, rated 6 A with a B-curve trip characteristic (magnetic trip at 4 x In ±20 %). The 36 kA Icu at 12–133 V AC (EN/IEC 60947-2) tells you it can safely interrupt a fault up to that level without welding contacts or cascading upstream; at 220–240 V AC that drops to 20 kA Icu, and at 380–415 V AC to 10 kA Icu. Dual-certified to both standards means it can be specified in industrial panels (60947-2) or final-distribution boards (60898-1) — the same part, different paperwork. ## Deployment context IP20 finger-safe front; the terminals accept up to 25 mm² rigid or 16 mm² flexible, with a 14 mm strip length and 2 N·m torque. Pollution degree 3 (conforms to 60947-2) rates it for conductive environments — typical in control panels. Overvoltage category IV, so it can be installed at the service entrance. No separate RoHS/REACH statement in the evidence, but Schneider Electric standard compliance documentation is available on request with the RFQ.","metaTitle":"Schneider Electric A9F03206 Acti9 iC60N MCB, 6 A, 2P, Curve","metaDescription":"Schneider Electric A9F03206 Acti9 iC60N miniature circuit-breaker, 6 A, 2-pole, curve B, 36 kA Icu at 12-133 V AC. Sourced to order against an RFQ. EN/IEC 60947-2 and 60898-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"6 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/95d0869d046ac8c8bc19861ada36f606.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F03206/miniature-circuit-breaker-mcb-acti9-ic60n-2p-6a-b-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F03206/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F03206?","answer":"36 kA Icu at 12–133 V AC, 20 kA Icu at 220–240 V AC, 10 kA Icu at 380–415 V AC, and 6 kA Icn at 400 V AC per EN/IEC 60898-1."},{"question":"What compliance documentation does A9F03206 carry?","answer":"Certified to EN/IEC 60947-2 and EN/IEC 60898-1, pollution degree 3, tropicalisation class 2, overvoltage category IV. Standard Schneider Electric compliance documentation is available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F03206","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F03206 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}