{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F03310","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F03310","canonicalUrl":"https://aoctrl.com/schneider/A9F03310","factsUrl":"https://aoctrl.com/api/mcp/products/A9F03310","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit breaker, A9F03310, B-curve, 10 A rated current, 3 poles, breaking capacity 36 kA Icu at 12...133 V AC, DIN rail mount, IP20.","salesMarkdown":"The Schneider Electric A9F03310 is a 3-pole miniature circuit breaker from the Acti9 iC60N range, rated 10 A with a B-curve trip characteristic. The 36 kA Icu at 12…133 V AC (per EN/IEC 60947-2) tells you it can safely interrupt a fault current up to 36 kA at those low voltages; at 220…240 V AC the rating drops to 20 kA, and at 380…415 V AC to 10 kA. The part also carries a 6 kA Icn at 400 V per EN/IEC 60898-1, which is the standard household/commercial breaking capacity for that standard. The 78.5 mm depth and 91 mm height are standard for the iC60N family, so it aligns with busbars and neighbouring devices in an Acti9 distribution board. Terminals accept 1…25 mm² rigid or 1…16 mm² flexible wire; strip length is 14 mm, torque to 2 N·m. The thermal-magnetic trip unit provides both overload (thermal) and short-circuit (magnetic) protection. A separate earth-leakage protection block can be added if needed.","metaTitle":"Schneider Electric A9F03310 Acti9 iC60N MCB, B-Curve 10 A 3P","metaDescription":"Schneider Electric A9F03310 Acti9 iC60N miniature circuit breaker, B-curve, 10 A, 3-pole, 36 kA breaking capacity at 133 V AC. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/724fc80ed598ee3769c4f06800c170a7.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F03310/miniature-circuit-breaker-mcb-acti9-ic60n-3p-10a-b-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F03310/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9F03310?","answer":"Pricing and availability are confirmed at quote time against an RFQ through independent distribution channels. Submit an RFQ for a current quote."},{"question":"What is A9F03310's breaking capacity at 400 V?","answer":"At 400 V AC 50/60 Hz, the A9F03310 has a breaking capacity of 10 kA Icu per EN/IEC 60947-2 and 6 kA Icn per EN/IEC 60898-1."},{"question":"What compliance documentation does this brand provide for A9F03310?","answer":"The part is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries tropicalisation class 2 per IEC 60068-1 and is rated for pollution degree 3 and overvoltage category IV."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F03310","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F03310 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}