{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F03313","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F03313","canonicalUrl":"https://aoctrl.com/schneider/A9F03313","factsUrl":"https://aoctrl.com/api/mcp/products/A9F03313","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit breaker, 13 A, 3P, curve B, 36 kA Icu at 12-133 V AC, DIN rail mount, white.","salesMarkdown":"The A9F03313 is a 13 A, 3-pole miniature circuit breaker from the Acti9 iC60N family, curve B. The curve B magnetic trip operates at 4 x In ±20 % (cites:), meaning it trips instantaneously between roughly 41.6 A and 62.4 A — suited for resistive or lightly inductive loads where inrush is low, such as lighting circuits or control transformers. The 36 kA Icu at 12-133 V AC (cites:) is the ultimate breaking capacity under EN/IEC 60947-2; at 400 V AC the Icn (rated short-circuit capacity per EN/IEC 60898-1) is 10 kA (cites:). ## Integration and deployment IP20 finger-safe terminals (cites:) are standard for enclosed distribution boards. Overvoltage category IV (cites:) confirms it can be used at the service entrance or main distribution point.","metaTitle":"Schneider Electric A9F03313 Acti9 iC60N MCB, 13 A, 3P, Curve","metaDescription":"Schneider Electric A9F03313 Acti9 iC60N miniature circuit breaker, 13 A, 3-pole, curve B, 36 kA breaking capacity at 12-133 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/80655cdd060999505fb8724413f9daf4.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F03313/miniature-circuit-breaker-mcb-acti9-ic60n-3p-13a-b-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F03313/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F03313 at 400 V AC?","answer":"At 400 V AC the Icn per EN/IEC 60898-1 is 10 kA (cites:). The Icu per EN/IEC 60947-2 at 380-415 V AC is also 10 kA (cites:)."},{"question":"What standards does A9F03313 comply with?","answer":"It complies with EN/IEC 60947-2 and EN/IEC 60898-1 (cites:). It is also suitable for isolation per both standards (cites:)."},{"question":"Where can I buy A9F03313?","answer":"The A9F03313 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F03313","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F03313 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}