{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F03325","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F03325","canonicalUrl":"https://aoctrl.com/schneider/A9F03325","factsUrl":"https://aoctrl.com/api/mcp/products/A9F03325","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F03325, miniature circuit breaker, 25 A, 3P, curve B, 36 kA Icu at 12-133 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F03325 is an Acti9 iC60N miniature circuit breaker, 25 A rated current, 3-pole, curve B. That curve B magnetic trip (4 x In ±20%) means it's sized for resistive or lighting loads where inrush is low — not motor starting or transformer primaries that'd nuisance-trip on a B curve. The 36 kA Icu at 12-133 V AC (EN/IEC 60947-2) gives it serious fault-clearing headroom on low-voltage distribution; at 220-240 V it still holds 20 kA. Dual-rated to both EN/IEC 60898-1 and EN/IEC 60947-2, so it qualifies for both domestic-panel and industrial panelboard specs. Snaps onto DIN rail (mounting support: DIN rail,). Three-pole, 54 mm wide — that's 6 x 9 mm pitches, so it fills six module positions on the rail. IP20 finger-safe front, pollution degree 3, overvoltage category IV — panel builders can land this in a main distribution board without derating for contamination.","metaTitle":"Schneider Electric A9F03325 Acti9 iC60N MCB, 25 A, 3P, Curve","metaDescription":"Schneider Electric A9F03325 Acti9 iC60N miniature circuit breaker, 25 A rated, 3-pole, curve B, 36 kA breaking capacity at 12-133 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/69bafa310f2368a40f5e57d84f78b801.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F03325/miniature-circuit-breaker-mcb-acti9-ic60n-3p-25a-b-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F03325/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the A9F03325?","answer":"25 A rated current, 3-pole, curve B magnetic trip (4 x In ±20%). Breaking capacity: 36 kA Icu at 12-133 V AC, 20 kA at 220-240 V AC, 10 kA at 380-415 V AC, 6 kA at 440 V AC per EN/IEC 60947-2; also rated 10 kA Icn at 400 V per EN/IEC 60898-1. Dual-standard certified to both EN/IEC 60947-2 and EN/IEC 60898-1."},{"question":"Where can I buy the A9F03325?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"What is the A9F03325's depth on the DIN rail?","answer":"Depth is 78.5 mm. Overall dimensions: 91 mm height, 54 mm width (6 module pitches)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F03325","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F03325 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}