{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F03413","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F03413","canonicalUrl":"https://aoctrl.com/schneider/A9F03413","factsUrl":"https://aoctrl.com/api/mcp/products/A9F03413","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N miniature circuit-breaker, A9F03413, 13 A, B curve, 4 poles, 36 kA Icu breaking capacity, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F03413 is an Acti9 iC60N miniature circuit-breaker rated 13 A with a B curve, 4 poles, and a 36 kA Icu breaking capacity at 12…133 V AC. The B curve means the magnetic trip fires at 4 x In ±20 % — 52 A nominal, 41.6 A to 62.4 A window. That suits resistive and general-purpose loads where you want a moderate inrush tolerance, not the high inrush of a C curve or the tight protection of a Z curve. At 220…240 V AC it drops to 20 kA Icu, and at 380…415 V AC to 10 kA Icu. The Icn (rated short-circuit capacity) per EN/IEC 60898-1 is 6 kA at 400 V AC. For a 13 A distribution MCB in a typical 400 V panel, the 6 kA Icn is the number that governs the installation standard. It carries dual certification to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household / similar), so it qualifies for both industrial control panels and building distribution boards. ## Deployment context The 4-pole format handles three-phase plus neutral in one unit — common for sub-distribution boards or machine supply panels. The IP20 finger-safe terminals are fine inside a closed enclosure; no washdown rating here.","metaTitle":"Schneider Electric A9F03413 Acti9 iC60N MCB, 13 A, B Curve,","metaDescription":"Schneider Electric A9F03413 Acti9 iC60N miniature circuit-breaker, 13 A, B curve, 4 poles, 36 kA breaking capacity, EN/IEC 60947-2 & 60898-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c2cffc771a3e7e82a32248a7b73c9187.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F03413/miniature-circuit-breaker-mcb-acti9-ic60n-4p-13a-b-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F03413/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9F03413?","answer":"Submit an RFQ — the part is sourced to order through independent distribution, with availability and current pricing confirmed at quote time."},{"question":"What is A9F03413's breaking capacity at 400 V?","answer":"The Icn per EN/IEC 60898-1 is 6 kA at 400 V AC; the Icu per EN/IEC 60947-2 is 10 kA at 380…415 V AC."},{"question":"What compliance standards does A9F03413 meet?","answer":"It is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with suitability for isolation per both standards. Pollution degree 3, overvoltage category IV, and tropicalisation class 2 per IEC 60068-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F03413","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F03413 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}