{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F03710","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F03710","canonicalUrl":"https://aoctrl.com/schneider/A9F03710","factsUrl":"https://aoctrl.com/api/mcp/products/A9F03710","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F03710, miniature circuit breaker, 10 A, B curve, 3P+N, 36 kA breaking capacity, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F03710 is an Acti9 iC60N miniature circuit breaker rated 10 A with a B curve, 3P+N poles, and a thermal-magnetic trip unit. It mounts on a DIN rail and is sized for distribution panels — 72 mm wide, 91 mm tall, 78.5 mm deep — so it occupies a standard 4-module footprint in a consumer unit or sub-distribution board. Rated for AC and DC networks at 50/60 Hz, it carries dual certification to EN/IEC 60898-1 (domestic MCB standard) and EN/IEC 60947-2 (industrial breaker standard), which means it can serve both residential final circuits and industrial control-panel feeder protection. The headline breaking capacity is 36 kA Icu at 12–133 V AC, dropping to 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V per IEC 60947-2. Under the domestic MCB standard (IEC 60898-1) it delivers 6000 A Icn at 400 V. The B curve means magnetic tripping occurs at 4 x In (±20 %), so a 10 A breaker trips instantaneously between roughly 32 A and 48 A. The double-terminal design accepts 1–25 mm² rigid or 1–16 mm² flexible on both top and bottom, with a tightening torque of 2 N·m and a strip length of 14 mm.","metaTitle":"Schneider Electric A9F03710 Acti9 iC60N MCB, 10 A, B Curve,","metaDescription":"Schneider Electric A9F03710 Acti9 iC60N miniature circuit breaker, 10 A rated, B curve, 3P+N, 36 kA breaking capacity, EN/IEC 60947-2 & 60898-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ac43530ce7134c80e4102b7eed60e4a9.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F03710/miniature-circuit-breaker-mcb-acti9-ic60n-3p+n-10a-b-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F03710/alternatives.json"},"ai":{"faq":[{"question":"What is A9F03710's breaking capacity at 400 V?","answer":"Under IEC 60898-1 it is rated 6000 A Icn at 400 V AC; under IEC 60947-2 it delivers 10 kA Icu at 380–415 V AC and 6 kA Icu at 440 V AC."},{"question":"What compliance documentation does Schneider provide for A9F03710?","answer":"The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1, carries IP20 protection per IEC 60529, and is tropicalised to class 2 per IEC 60068-1. Standard CE/UKCA marking applies for EU and UK markets."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F03710","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F03710 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}