{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F03713","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F03713","canonicalUrl":"https://aoctrl.com/schneider/A9F03713","factsUrl":"https://aoctrl.com/api/mcp/products/A9F03713","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N miniature circuit-breaker, A9F03713, 13 A rated, 3P+N, curve B, 36 kA Icu at 133 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"## What this MCB delivers The A9F03713 is a Schneider Electric Acti9 iC60N miniature circuit-breaker rated 13 A, 3P+N, curve B. Thermal-magnetic trip unit, so it handles both overload (thermal bimetal) and short-circuit (magnetic coil) protection in one package. Curve B means magnetic tripping occurs at 4 x In ±20 % — that is 52 A minimum — making it suited for resistive or lighting loads where inrush is low. The 36 kA Icu at 12…133 V AC (EN/IEC 60947-2) is the interrupting capacity under industrial fault conditions; the 6000 A Icn at 400 V (EN/IEC 60898-1) governs residential/commercial coordination. For a 13 A circuit, that is substantial headroom — selectivity with upstream devices is straightforward. Mounts on DIN rail, 72 mm wide (8 x 9 mm pitches). Suitability for isolation marked per both standards — pull the toggle and the contact position indicator confirms open. Overvoltage category IV (equipment at the origin of the installation, before the main distribution board).","metaTitle":"A9F03713 Acti9 iC60N MCB, 13 A, 3P+N, Curve B, 36 kA","metaDescription":"A9F03713 Acti9 iC60N miniature circuit-breaker, 13 A rated, 3P+N, curve B, 36 kA Icu at 133 V AC. Active production, sourced to order. Quoted against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f639fe413e84286e0051ca82b98dcad6.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F03713/miniature-circuit-breaker-mcb-acti9-ic60n-3p+n-13a-b-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F03713/alternatives.json"},"ai":{"faq":[{"question":"Who supplies A9F03713 and how is it quoted for volume purchases?","answer":"The A9F03713 is supplied through independent distribution channels. It is quoted to order against an RFQ — availability and current pricing are confirmed at quote time. Submit a request for volume pricing."},{"question":"What is A9F03713's breaking capacity at 400 V AC?","answer":"At 400 V AC, the A9F03713 has a rated short-circuit capacity of 6000 A Icn per EN/IEC 60898-1 and 10 kA Icu per EN/IEC 60947-2 at 380…415 V AC."},{"question":"What compliance documentation does this brand provide for A9F03713?","answer":"The A9F03713 is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries a CE mark for the European market. RoHS and REACH compliance documentation is available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F03713","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F03713 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}