{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F03716","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F03716","canonicalUrl":"https://aoctrl.com/schneider/A9F03716","factsUrl":"https://aoctrl.com/api/mcp/products/A9F03716","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N miniature circuit-breaker, A9F03716, 16 A rated, curve B, 3P+N, 36 kA breaking capacity at 133 V AC, DIN rail mount, thermal-magnetic trip.","salesMarkdown":"The Schneider Electric A9F03716 is an Acti9 iC60N miniature circuit-breaker (MCB) rated at 16 A, curve B, in a 3P+N (three-pole plus neutral) format. It is a thermal-magnetic trip device designed for distribution circuits in commercial and industrial panels. Its breaking capacity spans 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V AC, 10 kA at 380–415 V AC, and 6 kA at 440 V AC per EN/IEC 60947-2, plus a 6000 A Icn at 400 V AC per EN/IEC 60898-1. That dual rating means it qualifies for both industrial (60947-2) and residential/commercial (60898-1) applications — a single part number covers both compliance paths. The 3P+N format places the neutral pole on the left, with the three phase poles to its right. Double terminals top and bottom accept 1–25 mm² rigid or 1–16 mm² flexible cable; torque to 2 N·m. IP20 rated, so it belongs inside an enclosure — not exposed to washdown or outdoor weather.","metaTitle":"A9F03716 Acti9 iC60N MCB, 16 A, Curve B, 3P+N","metaDescription":"A9F03716 Acti9 iC60N miniature circuit-breaker, 16 A rated, curve B, 3P+N, 36 kA breaking capacity at 133 V AC. Dual-certified EN/IEC 60947-2 and 60898-1. DIN rail mount. Available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6578bf3513f0f13e7ba0fb8ea168375f.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F03716/miniature-circuit-breaker-mcb-acti9-ic60n-3p+n-16a-b-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F03716/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F03716 at 400 V?","answer":"At 400 V AC the A9F03716 delivers 10 kA Icu per EN/IEC 60947-2 and 6000 A Icn per EN/IEC 60898-1."},{"question":"Where can I buy A9F03716 and what is the lead time?","answer":"The A9F03716 is available to order through independent distribution. Submit an RFQ for current availability and pricing — lead time and stock are confirmed at quote time."},{"question":"What standards does the A9F03716 comply with?","answer":"It is dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/commercial), with suitability for isolation per both standards."},{"question":"What is the depth of A9F03716?","answer":"The depth is 78.5 mm, with a height of 91 mm and width of 72 mm (8 x 9 mm pitches)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F03716","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F03716 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}