{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04163","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04163","canonicalUrl":"https://aoctrl.com/schneider/A9F04163","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04163","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F04163, miniature circuit breaker, 1P, 63 A, C curve, 36 kA Icu at 12-60 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F04163 is a 1-pole Acti9 iC60N miniature circuit breaker rated 63 A with a C curve. Breaking capacity is 36 kA Icu at 12-60 V AC and 20 kA Icu at 100-133 V AC per EN/IEC 60947-2, with an Icn of 6 kA at 230 V AC per EN/IEC 60898-1. That 36 kA figure at low voltage means this breaker handles high prospective fault currents common in transformer-fed panels without cascading upstream. ## Trip curve and coordination The C curve has a magnetic tripping threshold of 8 x In ±20 %, so it holds through motor inrush and capacitive loads up to roughly 500 A instantaneous before tripping. This makes it a standard choice for general distribution where moderate inrush exists but not the high peaks of a D curve. ## Termination and environment Double terminals accept 1-35 mm² rigid or 1-25 mm² flexible cable, with a tightening torque of 3.5 N.m and strip length of 14 mm. The IP20 finger-safe front and tropicalisation level 2 per IEC 60068-1 (95 % RH at 55 °C) mean it holds up in humid panel environments without condensation tracking.","metaTitle":"Schneider Electric A9F04163 Acti9 iC60N MCB, 63 A, C Curve,","metaDescription":"Schneider Electric A9F04163 Acti9 iC60N miniature circuit breaker, 63 A rated current, C curve, 1 pole, 36 kA breaking capacity at 12-60 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"63 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/il/en/product/A9F04163/miniature-circuit-breaker-mcb-acti9-ic60n-1p-63a-c-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04163/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F04163?","answer":"The A9F04163 has a breaking capacity of 36 kA Icu at 12-60 V AC, 20 kA Icu at 100-133 V AC, and 10 kA Icu at 220-240 V AC per EN/IEC 60947-2, plus 6 kA Icn at 230 V AC per EN/IEC 60898-1."},{"question":"What standards does A9F04163 comply with?","answer":"The A9F04163 complies with EN/IEC 60947-2 and EN/IEC 60898-1, covering both industrial and domestic installation standards."},{"question":"Where can I buy A9F04163 and how is it quoted?","answer":"The A9F04163 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04163","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04163 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}