{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04225","canonicalUrl":"https://aoctrl.com/schneider/A9F04225","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit breaker, 25 A, 2P, C-curve, 36 kA Icu at 12-133 V AC, DIN rail mount, IP20.","salesMarkdown":"The Schneider Electric A9F04225 is an Acti9 iC60N miniature circuit breaker, rated 25 A, 2 poles, with a C-curve trip characteristic. It carries a 36 kA Icu breaking capacity at 12-133 V AC (per EN/IEC 60947-2) and a 10 kA Icn at 400 V AC (per EN/IEC 60898-1), making it suitable for distribution panel final circuits in commercial and light industrial builds. The 25 A C-curve means the magnetic trip activates between 5 and 10 times rated current (8 x In +/-20 % per spec), so it handles moderate inrush from motorized or fluorescent loads without nuisance tripping. Thermal-magnetic trip technology means bimetal for overload, solenoid for short-circuit — no electronics to fail. Overvoltage category IV and pollution degree 3 mean it's rated for the mains entrance of an installation — not just downstream sub-distribution. The IP20 finger-safe terminals suit enclosed panel mounting, not wet or dusty environments. Width is 36 mm (4 x 9 mm pitches), height 91 mm, depth 78.5 mm. Snaps onto standard DIN rail. The double terminals accept 1-25 mm² rigid or 1-16 mm² flexible, with a 2 N.m tightening torque and 14 mm strip length. Trip indicator shows local status; toggle control with contact position indicator for isolation verification (suitability for isolation confirmed per both standards).","metaTitle":"Schneider Electric A9F04225 Acti9 iC60N MCB, 25 A, 2P, C-Cur","metaDescription":"Schneider Electric A9F04225 Acti9 iC60N miniature circuit breaker, 25 A, 2 poles, C-curve, 36 kA breaking capacity at 12-133 V AC. DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8ad2683767f26007528b727126c9e7bd.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F04225/miniature-circuit-breaker-mcb-acti9-ic60n-2p-25a-c-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04225/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F04225?","answer":"The A9F04225 has a 36 kA Icu at 12-133 V AC, 20 kA Icu at 220-240 V AC, 10 kA Icu at 380-415 V AC, 6 kA Icu at 440 V AC (per EN/IEC 60947-2), and a 10 kA Icn at 400 V AC (per EN/IEC 60898-1)."},{"question":"Where can I buy A9F04225?","answer":"The A9F04225 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}