{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04310","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04310","canonicalUrl":"https://aoctrl.com/schneider/A9F04310","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04310","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 miniature circuit breaker, A9F04310, 10 A rated current, 3 poles, C curve, 36 kA breaking capacity at 133 V AC, DIN rail mount, white.","salesMarkdown":"The Schneider Electric A9F04310 is a 10 A, 3-pole miniature circuit breaker from the Acti9 iC60 series, with a C curve (magnetic trip at 8 x In ±20 %). Breaking capacity is the headline number here: 36 kA Icu at 12…133 V AC, 20 kA at 220…240 V, 10 kA at 380…415 V, and 6 kA at 440 V AC per EN/IEC 60947-2. It also carries a 10 kA Icn rating at 400 V per EN/IEC 60898-1. Snaps onto a DIN rail (mounting support: DIN rail). The 3-pole body takes 6 x 9 mm pitches — 54 mm wide, 91 mm tall, 78.5 mm deep. Terminals accept 1…25 mm² rigid or 1…16 mm² flexible wire; strip 14 mm and torque to 2 N·m. IP20 rated, so it's for inside a panel or enclosure, not for washdown areas. Dual-certified to EN/IEC 60898-1 (the household / commercial MCB standard) and EN/IEC 60947-2 (the industrial breaker standard). That means it passes both the 10 kA Icn test at 400 V for general use and the higher Icu tests for industrial coordination. Pollution degree 3, overvoltage category IV — suited for harsh electrical environments. Isolation-rated per both standards, so it can be used as a disconnecting means under load.","metaTitle":"Schneider Electric A9F04310 Acti9 iC60 Miniature Circuit Bre","metaDescription":"Schneider Electric A9F04310 Acti9 iC60 MCB, 10 A rated current, 3 poles, C curve. Breaking capacity 36 kA at 133 V AC. Compliant with EN/IEC 60947-2 and 60898-1. Available to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/855af3da030a473a47b6f6fe2f865f92.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F04310/miniature-circuit-breaker-mcb-acti9-ic60n-3p-10a-c-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04310/alternatives.json"},"ai":{"faq":[{"question":"What is A9F04310's listed depth (78.5 mm) on this component line?","answer":"The A9F04310 has a depth of 78.5 mm."},{"question":"What is A9F04310's listed range (Acti9) on this component line?","answer":"The A9F04310 belongs to the Acti9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04310","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04310 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}