{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04410","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04410","canonicalUrl":"https://aoctrl.com/schneider/A9F04410","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04410","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F04410, miniature circuit-breaker, 4P, 10 A, C-curve, 36 kA Icu at 12-133 V AC.","salesMarkdown":"The A9F04410 is a 10 A, 4-pole miniature circuit-breaker from the Schneider Electric Acti9 iC60N family. It is a thermal-magnetic MCB (trip unit technology: thermal-magnetic) with a C-curve (magnetic tripping limit 8 x In +/- 20 %), rated for both AC and DC networks at 50/60 Hz. The 36 kA Icu at 12-133 V AC (EN/IEC 60947-2) and 10 kA Icn at 400 V AC (EN/IEC 60898-1) tell you this breaker handles high short-circuit currents in a distribution panel — it's not a branch-circuit-only device. The dual-standard compliance (EN/IEC 60947-2 for industrial, EN/IEC 60898-1 for residential/commercial) means it qualifies for either type of installation, giving flexibility on the BOM. Mounts on DIN rail (mounting support: DIN rail), occupies 8 x 9 mm pitches (72 mm width) — standard 4-pole MCB footprint. Depth is 78.5 mm, height 91 mm. The double terminal accepts 1-25 mm² rigid or 1-16 mm² flexible, top or bottom. Tightening torque 2 N.m. Strip length 14 mm for both top and bottom connections. IP20 (conforms to IEC 60529) — suitable for enclosed distribution boards only, not washdown areas. Rated current 10 A (In) — this is the continuous load it can carry without tripping. C-curve (magnetic trip at 8 x In, +/- 20 %) means it holds through motor inrush up to about 80 A before the magnetic coil trips; good for lighting panels or mixed loads with moderate starting currents, not for heavy motor starts (that would want a D-curve). Breaking capacity: 36 kA Icu at 12-133 V AC, 20 kA at 220-240 V AC, 10 kA at 380-415 V AC, 6 kA at 440 V AC (all per EN/IEC 60947-2). The 10 kA Icn at 400 V AC (EN/IEC 60898-1) is the standard residential/commercial rating. The 36 kA figure at lower voltages means this breaker can be used on 110 V panels with high fault current — useful in industrial control panels fed from a 110 V control transformer with high SCCR. Overvoltage category IV — for main distribution boards. Suitability for isolation: yes, per both standards, so it can be used as a disconnecting means.","metaTitle":"Schneider Electric A9F04410 Acti9 iC60N MCB, 10 A, C-Curve,","metaDescription":"Schneider Electric A9F04410 Acti9 iC60N miniature circuit-breaker, 10 A rated, C-curve, 4-pole, 36 kA breaking capacity at 12-133 V AC. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a1eba64bab91b4a64ae19acd39e4a56f.pdf","sourceUrl":"https://www.se.com/il/en/product/A9F04410/miniature-circuit-breaker-mcb-acti9-ic60n-4p-10a-c-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04410/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to A9F04410 in the Acti9 family?","answer":"Within the same Acti9 iC60 range, the closest sibling is the same 10 A, 4P, C-curve MCB with a different breaking capacity or a different curve (B or D). The physical footprint (DIN rail, 72 mm width) and terminal specs are identical; the difference is the short-circuit rating or trip curve. If you need the same 10 A, 4P, C-curve with a different breaking capacity, look at the iC60H or iC60L variants — they share the same dimensions and connections."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04410","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04410 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}