{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04432","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04432","canonicalUrl":"https://aoctrl.com/schneider/A9F04432","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04432","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F04432, miniature circuit-breaker, 4P, 32 A, C-curve, 10 kA Icn at 400 V AC, thermal-magnetic, DIN rail.","salesMarkdown":"## 32 A C-curve MCB for distribution boards The Schneider A9F04432 is an Acti9 iC60N miniature circuit-breaker rated 32 A with a C-curve magnetic trip at 8 x In (+/- 20 %). Four poles, thermal-magnetic trip unit, DIN-rail mount. Dual-rated to EN/IEC 60947-2 (Category A) and EN/IEC 60898-1, so it carries both the industrial and residential certification — useful when the same BOM feeds panel builds and final distribution boards. Breaking capacity follows the voltage: 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, 6 kA at 440 V (all per EN/IEC 60947-2). The IEC 60898-1 rating is 10 kA Icn at 400 V AC — that's the number most distribution specs will reference. Overvoltage category IV, pollution degree 3, so it's rated for the mains entry, not just sub-distribution. Lifecycle stage is current — no NRND or phase-out signal on this order code. The Acti9 iC60 series is Schneider's mainstream MCB line; the A9F04432 is an active catalog number. Mounts on DIN rail, 9 mm pitches: 8 modules wide (72 mm). Height 91 mm, depth 78.5 mm. Tightening torque 3.5 N·m. Wire strip length 14 mm. IP20 finger-safe. The white body with toggle and trip indicator makes visual status checks fast during commissioning or fault-finding. Electrical endurance 10,000 cycles, mechanical 20,000 cycles. Rated for isolation per both IEC 60898-1 and 60947-2 — the contact position indicator and positive break confirm the circuit is open. Suits non-condensing environments in panel builds for industrial or commercial distribution.","metaTitle":"Schneider A9F04432 Acti9 iC60N MCB, 32 A, C-Curve, 4P, 10 kA","metaDescription":"Schneider A9F04432 Acti9 iC60N miniature circuit-breaker, 32 A rated, C-curve, 4 poles, 10 kA breaking capacity at 400 V AC. Dual-rated to EN/IEC 60947-2 and 60898-1. Current produ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/faa9ff34c27cb55dbf76ead3c93fabcb.pdf","sourceUrl":"https://www.se.com/il/en/product/A9F04432/miniature-circuit-breaker-mcb-acti9-ic60n-4p-32a-c-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04432/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9F04432 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price."},{"question":"What is the breaking capacity of the A9F04432 at 400 V?","answer":"10 kA Icn at 400 V AC per EN/IEC 60898-1. Per EN/IEC 60947-2, the Icu at 380–415 V AC is also 10 kA."},{"question":"What standards does the A9F04432 comply with?","answer":"Dual-rated to EN/IEC 60947-2 and EN/IEC 60898-1. Also conforms to IEC 60529 (IP20), IEC 60068-1 (tropicalisation class 2), and pollution degree 3 per EN/IEC 60947-2."},{"question":"What is the magnetic trip threshold on the A9F04432?","answer":"C-curve: magnetic tripping at 8 x In +/- 20 %. For the 32 A rating, that's 256 A nominal, with a tolerance band of roughly 205–307 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04432","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04432 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}