{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04463","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04463","canonicalUrl":"https://aoctrl.com/schneider/A9F04463","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04463","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 miniature circuit breaker, A9F04463, thermal-magnetic trip unit, 63 A rated current, curve C, 4 poles, breaking capacity 36 kA Icu at 12-133 V AC.","salesMarkdown":"The Schneider Electric A9F04463 is an Acti9 iC60 miniature circuit breaker (MCB) with a 63 A rated current, curve C trip characteristic, and 4 poles. It is a thermal-magnetic device rated for both AC and DC networks, with a breaking capacity of 36 kA Icu at 12-133 V AC 50/60 Hz per EN/IEC 60947-2. Mounts on DIN rail per. The 4-pole footprint occupies 8 x 9 mm pitches (72 mm wide), so it fills four module positions in a distribution board. Height is 91 mm, depth 78.5 mm — check gland plate clearance if the enclosure is shallow. Certified to both EN/IEC 60898-1 and EN/IEC 60947-2. That dual standard coverage means it qualifies for residential/commercial distribution (60898-1) and industrial panel use (60947-2) — no ambiguity about which code cycle accepts it. Overvoltage category IV, pollution degree 3 — rated for the main incoming supply, not just sub-circuits.","metaTitle":"Schneider Electric A9F04463 Acti9 iC60 MCB, 63 A, Curve C, 4","metaDescription":"Schneider Electric A9F04463 Acti9 iC60 miniature circuit breaker, 63 A rated current, curve C, 4 poles. Breaking capacity 36 kA Icu at 12-133 V AC. Current lifecycle stage. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"63 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9d79ec51c02497ecc6d6339e0b09515e.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F04463/miniature-circuit-breaker-mcb-acti9-ic60n-4p-63a-c-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04463/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F04463?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What are the key specifications of A9F04463?","answer":"63 A rated current, curve C, 4 poles, thermal-magnetic trip. Breaking capacity 36 kA Icu at 12-133 V AC per EN/IEC 60947-2. Magnetic tripping limit 8 x In ±20%. DIN rail mount, IP20."},{"question":"What compliance documentation does the brand provide for A9F04463?","answer":"The part is certified to EN/IEC 60898-1 and EN/IEC 60947-2. Suitability for isolation confirmed under both standards. Overvoltage category IV, pollution degree 3. The manufacturer typically provides a declaration of conformity; request it with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04463","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04463 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}