{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04650","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04650","canonicalUrl":"https://aoctrl.com/schneider/A9F04650","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04650","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit breaker, A9F04650, 50 A, C curve, 1P+N, 36 kA breaking capacity, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F04650 is an Acti9 iC60N miniature circuit breaker rated 50 A with a C curve, 1P+N configuration, and a breaking capacity of 36 kA Icu at 12...60 V AC. At 220...240 V AC it's 10 kA Icu, and under the domestic-standard EN/IEC 60898-1 it's 6000 A Icn at 230 V. For a 50 A distribution board fed from a transformer of modest size, 10 kA at 240 V is usually adequate; the 36 kA figure matters if this sits close to a high-capacity source (large transformer or generator bus). The dual standard means it's accepted in both industrial (60947-2) and residential/commercial (60898-1) specifications — one part number for both worlds. ## Panel integration Snaps onto standard DIN rail. Width is 36 mm (4 x 9 mm pitches), which is the standard single-module width for a 1P+N MCB — no surprise for panel layout. Strip length 14 mm, torque to 3.5 N.m. IP20 finger-safe front, pollution degree 3 rated — fine for most industrial control panels, but not for washdown zones.","metaTitle":"Schneider Electric A9F04650 Acti9 iC60N MCB, 50 A, C Curve,","metaDescription":"Schneider Electric A9F04650 Acti9 iC60N miniature circuit breaker, 50 A rated current, C curve, 1P+N, 36 kA breaking capacity at 12-60 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"50 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8306714c137af231d187599ae05f34dd.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F04650/miniature-circuit-breaker-mcb-acti9-ic60n-1p+n-50a-c-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04650/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F04650 at 240 V?","answer":"At 220...240 V AC, the breaking capacity is 10 kA Icu per EN/IEC 60947-2, and 6000 A Icn at 230 V per EN/IEC 60898-1."},{"question":"What wire sizes does the A9F04650 terminal accept?","answer":"Double terminals top and bottom accept 1...35 mm² rigid or 1...25 mm² flexible copper. Strip length is 14 mm, torque to 3.5 N.m."},{"question":"Where can I buy A9F04650 and get current pricing?","answer":"The A9F04650 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04650","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04650 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}