{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04701","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04701","canonicalUrl":"https://aoctrl.com/schneider/A9F04701","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04701","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F04701, miniature circuit breaker, 1 A rated current, C-curve, 3 poles + neutral, 50 kA breaking capacity, DIN rail mount, thermal-magnetic trip.","salesMarkdown":"The Schneider Electric A9F04701 is an Acti9 iC60N miniature circuit breaker — 1 A rated, C-curve, 3 poles plus neutral, thermal-magnetic trip unit. It carries a 50 kA breaking capacity (Icu) at 220…240 V AC, dropping to 25 kA at 440 V AC, and 6 kA Icn per EN/IEC 60898-1 at 400 V. That dual standard (EN/IEC 60947-2 and 60898-1) means it qualifies for both industrial panel protection and building distribution — the 60947-2 rating is what matters for the SCCR declaration on a machine nameplate. Snaps onto DIN rail, occupies 8 x 9 mm pitches (72 mm wide). The 78.5 mm depth leaves clearance in a standard 100 mm enclosure — no tight squeeze for the gland plate. Wire strip to 14 mm. Neutral is fixed left; the toggle gives local indication plus a trip flag.","metaTitle":"Schneider Electric A9F04701 Acti9 iC60N MCB, 1 A C-Curve, 3P","metaDescription":"Schneider Electric A9F04701 Acti9 iC60N miniature circuit breaker, 1 A rated, C-curve, 3P+N, 50 kA breaking capacity, DIN rail. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"1 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6e0d93f8b52876b21bdfdea1d531d979.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F04701/miniature-circuit-breaker-mcb-acti9-ic60n-3p+n-1a-c-curve-6000a-iec-608981-50ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04701/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F04701 and get a price?","answer":"The A9F04701 is sourced to order against an RFQ through independent distribution. Submit a request with your quantity and target delivery window; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of A9F04701?","answer":"The A9F04701 delivers 50 kA Icu at 220…240 V AC and 380…415 V AC per EN/IEC 60947-2, 25 kA Icu at 440 V AC, and 6 kA Icn at 400 V AC per EN/IEC 60898-1. That dual rating covers both industrial panel SCCR and building-distribution fault levels."},{"question":"What does the C-curve magnetic trip mean on A9F04701?","answer":"The C-curve trips magnetically at 8 x In ±20 % — that is 8 A to 9.6 A for this 1 A breaker. It is the standard choice for general-purpose distribution loads where inrush is moderate (lighting, small transformers, control circuits), not high-inrush motor starts."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04701","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04701 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}