{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04702","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04702","canonicalUrl":"https://aoctrl.com/schneider/A9F04702","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04702","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F04702, miniature circuit breaker, 2 A, C-curve, 3P+N, 50 kA Icu at 415 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F04702 is an Acti9 iC60N miniature circuit breaker rated 2 A with a C-curve (magnetic trip at 8 x In ±20%, so 16 A typical instantaneous pickup). The same part is also rated 6 kA Icn at 400 V per EN/IEC 60898-1, the domestic-standard marking. Dual-rated means it qualifies for both industrial (60947-2) and residential/commercial (60898-1) installations — useful when a BOM crosses building code boundaries. The neutral position is left, which matters when aligning busbar comb fingers in a multi-pole assembly. DIN-rail mount, 72 mm wide (8 x 9 mm pitches), so it occupies standard panel space. ## Integration notes Tightening torque 2 N·m. Wire strip length 14 mm. IP20 finger-safe front, pollution degree 3 (conductive pollution environment, typical for industrial panels). Overvoltage category IV — suitable for main incoming supply.","metaTitle":"Schneider Electric A9F04702 Acti9 iC60N MCB, 2 A, C-Curve, 3","metaDescription":"Schneider Electric A9F04702 Acti9 iC60N miniature circuit breaker, 2 A rated current, C-curve, 3P+N, 50 kA Icu at 415 V AC. Dual-rated to EN/IEC 60947-2 and 60898-1. Available to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"2 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/71802f3c4c9f57163b02ce055779bad9.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F04702/miniature-circuit-breaker-mcb-acti9-ic60n-3p+n-2a-c-curve-6000a-iec-608981-50ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04702/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the A9F04702?","answer":"50 kA Icu at 380–415 V AC per EN/IEC 60947-2, and 6 kA Icn at 400 V per EN/IEC 60898-1. The 50 kA figure governs industrial coordination; the 6 kA figure is the domestic-standard rating."},{"question":"Where can I buy the A9F04702?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What standards does the A9F04702 comply with?","answer":"Dual-rated to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/commercial). Also conforms to IEC 60068-1 for tropicalisation (2-level) and IEC 60529 for IP20 protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04702","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04702 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}