{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04710","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04710","canonicalUrl":"https://aoctrl.com/schneider/A9F04710","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04710","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit breaker, A9F04710, 10 A, 3P+N, C-curve, breaking capacity 36 kA Icu at 12-133 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F04710 is an Acti9 iC60N miniature circuit breaker rated at 10 A with a C-curve, 3P+N poles, and a breaking capacity of 36 kA Icu at 12-133 V AC. Rated to both EN/IEC 60898-1 and EN/IEC 60947-2, this MCB delivers 36 kA Icu at 12-133 V AC, 20 kA Icu at 220-240 V AC, and 10 kA Icu at 380-415 V AC. The C-curve magnetic trip triggers at 8 x In (±20%), handling typical motor and lighting inrush without nuisance tripping. Snaps onto a DIN rail, occupies 8 x 9 mm pitches (72 mm wide), and stands 91 mm tall with a depth of 78.5 mm. IP20 finger-safe protection suits enclosed panel installation.","metaTitle":"Schneider Electric A9F04710 Acti9 iC60N MCB, 10 A, 3P+N, C-C","metaDescription":"Schneider Electric A9F04710 Acti9 iC60N miniature circuit breaker, 10 A rated, 3P+N, C-curve, 36 kA breaking capacity at 12-133 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4cc46089fbcc907d2dbe14714d8b8273.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F04710/miniature-circuit-breaker-mcb-acti9-ic60n-3p+n-10a-c-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04710/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F04710 and how do I get a price?","answer":"The A9F04710 is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is A9F04710's listed depth?","answer":"The A9F04710 has a depth of 78.5 mm."},{"question":"What is A9F04710's listed range?","answer":"The A9F04710 belongs to the Acti9 range."},{"question":"What compliance documentation does this brand provide for A9F04710?","answer":"The A9F04710 complies with EN/IEC 60947-2 and EN/IEC 60898-1 standards, with tropicalisation class 2 per IEC 60068-1 and pollution degree 3 per EN/IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04710","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04710 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}