{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F04770","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F04770","canonicalUrl":"https://aoctrl.com/schneider/A9F04770","factsUrl":"https://aoctrl.com/api/mcp/products/A9F04770","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 miniature circuit-breaker, A9F04770, 0.5 A rated current, C-curve, 3P+N, 50 kA Icu at 415 V AC, DIN rail mount, white.","salesMarkdown":"The A9F04770 is a Schneider Electric Acti9 iC60 miniature circuit-breaker (MCB) rated at 0.5 A with a C-curve, 3 poles plus neutral, and a breaking capacity of 50 kA Icu at 415 V AC. The C-curve magnetic trip operates at 8 x In ±20 % per the spec. Rated Icu of 50 kA at 220–415 V AC per EN/IEC 60947-2, with a 6000 A Icn per EN/IEC 60898-1 at 400 V. The dual rating means it qualifies for both industrial (60947-2) and residential/commercial (60898-1) applications — useful when the same panel feeds mixed loads and the inspector wants a single part number for the BOM. Overvoltage category IV means it can be installed at the service entrance or main distribution board. ## Integration notes The 72 mm width (8 x 9 mm pitches) fits a standard 4-module slot in a distribution board. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible wire; strip length 14 mm, torque to 2 N·m. The white housing and toggle actuator are standard for the Acti9 range; the trip indicator gives local visual confirmation of a tripped state.","metaTitle":"A9F04770 Acti9 iC60 MCB, 0.5 A C-curve, 3P+N, 50 kA Icu","metaDescription":"A9F04770 Acti9 iC60 miniature circuit-breaker, 0.5 A rated current, C-curve, 3P+N, 50 kA Icu at 415 V AC, DIN rail mount, current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"0.5 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a9865510ee64a6692c32b2b02d2b9900.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F04770/miniature-circuit-breaker-mcb-acti9-ic60n-3p+n-0-5a-c-curve-6000a-iec-608981-50ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F04770/alternatives.json"},"ai":{"faq":[{"question":"What is A9F04770's breaking capacity?","answer":"50 kA Icu at 220–415 V AC per EN/IEC 60947-2, and 6000 A Icn at 400 V per EN/IEC 60898-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F04770","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F04770 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}