{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05106","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05106","canonicalUrl":"https://aoctrl.com/schneider/A9F05106","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05106","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F05106, miniature circuit breaker, 1P, 6 A, D curve, 36 kA breaking capacity, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"At 230 V AC the A9F05106 carries a 6 kA Icn rating per EN/IEC 60898-1, but under EN/IEC 60947-2 it's rated 36 kA Icu at 12-60 V AC, 20 kA at 100-133 V AC, and 10 kA at 220-240 V AC. On the DC side it handles 15 kA at 12-60 V DC and 10 kA at 60-72 V DC. That spread means it can be applied in low-voltage industrial control panels where fault currents are higher than a standard residential panel, and still coordinate with downstream loads. Snaps onto a standard DIN rail — 18 mm width (2 x 9 mm pitches), 91 mm tall, 78.5 mm deep. The double-terminal design on top and bottom accepts 1-25 mm² rigid or 1-16 mm² flexible, with a stripping length of 14 mm and a tightening torque of 2 Nm. IP20 finger-safe terminals are fine for enclosed panels; keep it behind a door or cover in a washdown area.","metaTitle":"Schneider Electric A9F05106 Acti9 iC60N MCB, 6A D Curve, 1P","metaDescription":"Schneider Electric A9F05106 Acti9 iC60N miniature circuit breaker, 6A rated, D curve, 1 pole. 36 kA breaking capacity. Quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"6 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5f0244ba1e7258b869cf66b842302437.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05106/miniature-circuit-breaker-mcb-acti9-ic60n-1p-6a-d-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05106/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9F05106 and get a price?","answer":"The A9F05106 is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — no stock count or price is published here."},{"question":"What is the breaking capacity of the A9F05106?","answer":"At 230 V AC the breaker is rated 6 kA Icn per EN/IEC 60898-1. Under EN/IEC 60947-2 it achieves 36 kA Icu at 12-60 V AC, 20 kA at 100-133 V AC, and 10 kA at 220-240 V AC. On DC it handles 15 kA at 12-60 V DC and 10 kA at 60-72 V DC."},{"question":"What standards does the A9F05106 comply with?","answer":"It is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with a pollution degree of 3, overvoltage category IV, and suitability for isolation per both standards. Tropicalisation class 2 per IEC 60068-1 is also listed."},{"question":"What is the D curve on the A9F05106 for?","answer":"The D curve trips magnetically at 12 x In (72 A for this 6 A breaker), +/-20%. It is intended for loads with high inrush currents such as small motors, transformers, and solenoid valves where a B or C curve would nuisance-trip on startup."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05106","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05106 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}