{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05113","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05113","canonicalUrl":"https://aoctrl.com/schneider/A9F05113","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05113","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F05113, miniature circuit breaker, 1P, 13 A, D curve, 10 kA Icn at 230 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F05113 is an Acti9 iC60N miniature circuit breaker — 1-pole, 13 A rated current, D-curve trip characteristic. On a 230 V AC supply the breaking capacity is 10 kA Icn per EN/IEC 60898-1; at 240 V AC it holds 10 kA Icu per EN/IEC 60947-2. That dual certification (both the household-standard 60898-1 and the industrial-standard 60947-2) lets the same part serve residential distribution boards and industrial panel builds — one BOM line for both worlds. ## DIN-rail integration and panel fit Depth of 78.5 mm and height of 91 mm keep the profile within typical enclosure clearance. ## Selectivity and coordination notes Suitability for isolation (marked per both standards) means it can serve as a disconnecting means in the circuit without a separate isolator.","metaTitle":"Schneider Electric A9F05113 Acti9 iC60N MCB, 13 A, 1P, D Cur","metaDescription":"Schneider Electric A9F05113 Acti9 iC60N miniature circuit breaker, 13 A, 1-pole, D curve, 10 kA at 230 V AC. Dual certified to EN/IEC 60947-2 and 60898-1. Active production, availa","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9ec745193aa3761aad0ee38d3feca2f3.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05113/miniature-circuit-breaker-mcb-acti9-ic60n-1p-13a-d-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05113/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F05113 at 230 V AC?","answer":"10 kA Icn at 230 V AC per EN/IEC 60898-1, and 10 kA Icu at 220–240 V AC per EN/IEC 60947-2."},{"question":"What compliance documentation does Schneider provide for A9F05113?","answer":"The breaker is dual-certified to EN/IEC 60947-2 and EN/IEC 60898-1, carries IP20 protection, and is tropicalised to IEC 60068-1 (class 2)."},{"question":"Where can I buy A9F05113 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock figures or price lists published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05113","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05113 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}