{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05116","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05116","canonicalUrl":"https://aoctrl.com/schneider/A9F05116","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05116","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F05116, miniature circuit breaker, 1P, 16 A, D-curve, 36 kA Icu at 12-60 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The D-curve means its magnetic trip threshold is 12 x In ±20% — so it holds through the inrush of motor or transformer loads without nuisance tripping, then clears a hard fault fast. This is the MCB you spec for a motor branch or a high-starting-current circuit in a distribution board. Rated at 36 kA Icu at 12-60 V AC (EN/IEC 60947-2) and 20 kA Icu at 100-133 V AC, the A9F05116 handles high prospective fault currents common in industrial panels. At 230 V AC the Icn rating under EN/IEC 60898-1 is 6000 A, which covers residential and light commercial final circuits. It carries dual certification — EN/IEC 60947-2 for industrial isolation and EN/IEC 60898-1 for domestic installation — so the same part works across both worlds. Overvoltage category IV means it's rated for the main incoming supply, not just sub-circuits. Width is 18 mm (2 x 9 mm pitches), so it occupies one modular space in a distribution board. The double terminal accepts 1-25 mm² rigid or 1-16 mm² flexible cable top and bottom; strip length is 14 mm. IP20 finger-safe terminals — fine for enclosed panels; keep it behind a locked door. The A9F05116 is an active catalogue line within the Acti9 range, so factory supply is stable. Same part, different passport — genuine is genuine, and we move it through independent channels that keep the BOM line filled without the premium of an authorised-distributor-only route.","metaTitle":"A9F05116 Acti9 iC60N MCB, 16 A, 1P, Curve D, 36 kA Icu","metaDescription":"Schneider Electric A9F05116 Acti9 iC60N miniature circuit breaker, 16 A, 1-pole, curve D, 36 kA Icu at 12-60 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/70c86aa195f4cf81efcfdc6544ba7ce4.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05116/miniature-circuit-breaker-mcb-acti9-ic60n-1p-16a-d-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05116/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F05116 and what is the lead time?","answer":"The A9F05116 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number on this page, but we can give you a firm position on request."},{"question":"What is the breaking capacity of A9F05116 at 230 V?","answer":"At 230 V AC the Icn rating under EN/IEC 60898-1 is 6000 A. Under EN/IEC 60947-2 the Icu at 220-240 V AC is 10 kA."},{"question":"What compliance documentation does A9F05116 carry?","answer":"The A9F05116 is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries IP20 protection (IEC 60529), pollution degree 3, and tropicalisation class 2 per IEC 60068-1. Isolation suitability is confirmed under both standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05116","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05116 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}