{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05132","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05132","canonicalUrl":"https://aoctrl.com/schneider/A9F05132","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05132","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F05132, miniature circuit breaker, 1-pole, 32 A, D curve, 36 kA breaking capacity at 12-60 VAC, DIN rail mount.","salesMarkdown":"Breaking capacity reaches 36 kA Icu at 12-60 VAC (per EN/IEC 60947-2), which covers most industrial control panel fault levels. At 220-240 VAC the rating drops to 10 kA Icu, still adequate for standard distribution boards. The part carries dual certification to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/commercial), giving you flexibility to spec it across plant and facility applications under one catalog number. The 18 mm width per pole keeps panel density predictable. IP20 finger-safe front protects operators in open-panel environments. Rated insulation voltage is 500 VAC, overvoltage category IV, pollution degree 3 — suited for main distribution panels where transient overvoltages are a concern. Thermal-magnetic trip unit with a trip indicator provides local visual confirmation of a faulted circuit. Contact position indicator confirms the main contacts are open — useful during lockout/tagout verification. The part is suitability-for-isolation certified per both EN/IEC 60898-1 and EN/IEC 60947-2, meaning it can be used as a disconnecting means where local codes require it.","metaTitle":"Schneider Electric A9F05132 Acti9 iC60N MCB, 32 A, 1P, D Cur","metaDescription":"Schneider Electric A9F05132 Acti9 iC60N miniature circuit breaker, 32 A rated current, 1-pole, D curve, 36 kA breaking capacity at 12-60 VAC. Dual-rated to EN/IEC 60947-2 and 60898","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8f0f59c3a62f3a94df153d9db45ca36a.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05132/miniature-circuit-breaker-mcb-acti9-ic60n-1p-32a-d-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05132/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05132","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05132 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}