{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05210","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05210","canonicalUrl":"https://aoctrl.com/schneider/A9F05210","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05210","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit breaker, 10 A, D curve, 2P, 36 kA breaking capacity, DIN rail.","salesMarkdown":"The Schneider Electric A9F05210 is an Acti9 iC60N miniature circuit breaker rated 10 A with a D tripping curve, 2 poles, and a 36 kA Icu breaking capacity at 12–133 V AC. The 36 kA Icu at 12–133 V AC drops to 20 kA at 220–240 V and 10 kA at 380–415 V. That 10 kA at 400 V matches the Icn under 60898-1, so the breaker is coordinated for a standard 10 kA prospective fault level at 400 V three-phase. The 6 kA Icu at 440 V AC covers the upper end of the 400 V tolerance band. Snaps onto a 36 mm wide DIN rail — that's 4 module pitches (9 mm each). The double terminals accept 1–25 mm² rigid or 1–16 mm² flexible copper, with a 14 mm strip length and 2 N·m tightening torque. The toggle actuator and trip indicator give local status; the contact position indicator confirms isolation (certified per both standards).","metaTitle":"Schneider Electric A9F05210 Acti9 iC60N MCB, 10 A, D Curve,","metaDescription":"Schneider Electric A9F05210 Acti9 iC60N miniature circuit breaker, 10 A rated current, D curve, 2-pole, 36 kA breaking capacity, DIN rail mount. Current lifecycle stage, sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c52c2ac70aaac87c3cfa8f1e46c2e8cd.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05210/miniature-circuit-breaker-mcb-acti9-ic60n-2p-10a-d-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05210/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F05210 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is A9F05210's listed depth (78.5 mm) on this component line?","answer":"The depth is 78.5 mm, with a height of 91 mm and a width of 36 mm (4 x 9 mm pitches)."},{"question":"What is A9F05210's listed range (Acti9) on this component line?","answer":"It belongs to the Acti9 range, specifically the iC60N series of miniature circuit breakers."},{"question":"What compliance documentation does this brand provide for A9F05210 (RoHS, REACH, UL, IEC)?","answer":"The MCB is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries IP20 protection and is tropicalised to IEC 60068-1 (class 2)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05210","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05210 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}