{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05301","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05301","canonicalUrl":"https://aoctrl.com/schneider/A9F05301","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05301","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N miniature circuit breaker, A9F05301, D curve, 1 A, 3-pole, 50 kA breaking capacity at 415 V AC, DIN rail mount.","salesMarkdown":"Snaps onto a DIN rail (mounting support: DIN rail). The 3-pole footprint takes 6 x 9 mm pitches — 54 mm wide — so it occupies three standard modular positions in the enclosure. Double terminals top and bottom accept 1…25 mm² rigid or 1…16 mm² flexible; torque to 2 N·m. IP20 finger-safe front, pollution degree 3, overvoltage category IV — rated for main distribution panels, not just sub-distribution. Compliant with both EN/IEC 60898-1 (domestic / commercial MCB standard) and EN/IEC 60947-2 (industrial circuit-breaker standard). That dual certification means it can be specified in residential consumer units (60898-1) or industrial panelboards (60947-2) without a separate part number. Isolation suitability is confirmed under both standards.","metaTitle":"Schneider Electric A9F05301 Acti9 iC60N MCB, D Curve 1 A 3P","metaDescription":"Schneider Electric A9F05301 Acti9 iC60N miniature circuit breaker, 1 A rated current, D curve, 3 poles, 50 kA breaking capacity at 415 V AC. Active production, sourced to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"1 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8d83442ee2de68d26a2e1e96ebaedaf5.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05301/miniature-circuit-breaker-mcb-acti9-ic60n-3p-1a-d-curve-6000a-iec-608981-50ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05301/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F05301?","answer":"50 kA Icu at 415 V AC (per EN/IEC 60947-2), and 10 kA Icn at 400 V AC (per EN/IEC 60898-1)."},{"question":"Where can I buy A9F05301?","answer":"Sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the D curve on A9F05301 used for?","answer":"The D curve (magnetic trip at 12 x In) is designed for loads with high inrush current — motor starters, transformers, welding equipment — where a B or C curve would nuisance-trip on startup."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05301","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05301 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}